38059-Satchwell Inter. Guide 05
38059-Satchwell Inter. Guide 05
38059-Satchwell Inter. Guide 05
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Satchwell</strong> Controllers<br />
Keyboard<br />
MMC 4701<br />
Universal Air<br />
Handling Unit<br />
Controller<br />
MMC 4601<br />
Multi-loop District<br />
Heating Controller<br />
Terminal Unit<br />
CZU<br />
Fan Coil Unit<br />
Controller<br />
This PID Controller can be used to control humidity or<br />
temperature in various ventilation and air conditioning<br />
system applications.<br />
The serial link function allows the MMC to be fully<br />
integrated into a networking system with all the advantages<br />
of remote monitoring, alarms, logging, graphics and remote<br />
setting of all control parameters. The MMC can work as a<br />
fully stand-alone controller.<br />
The controller can be configured to run in one of the<br />
applications by simply selecting that application number.<br />
1. Single Stage Temperature Controller<br />
2. Two Stage Temperature Controller<br />
3. Three Stage Temperature Controller<br />
4. Three Stage Room Temperature Reset Controller with<br />
Heat Recovery<br />
5. Three Stage Cascade Temperature Controller<br />
6. Single Stage Temperature Controller<br />
(24Vac Actuator Output)<br />
7. Single Stage Humidity Controller<br />
8. Two Stage Humidity Controller<br />
9. Simple Single Stage Temperature Controller<br />
10. Simple Two Stage Temperature Controller<br />
11. Simple Three Stage Temperature Controller<br />
The MMC is a Multi-loop Controller for use in district<br />
heating schemes.<br />
The controller incorporates three separate control loops, two<br />
compensated and the other a constant temperature loop.<br />
Up to 3 specific points are programmed for the<br />
compensation graph. The MMC automatically joins up these<br />
points to produce a user defined compensation curve. This<br />
adjusts and calculates the required set value of the supply<br />
temperature to the compensated system to match the<br />
prevailing requirements.<br />
The MMC has a self tuning function that allows each of the<br />
3 control loops to have its proportional band, integral action<br />
and derivative action values automatically tuned. Self tuning<br />
can be carried out from the MMC keyboard or from<br />
optional external momentary switches connected to it. Self<br />
tuning maximises the efficiency of control loop operation.<br />
FEATURES<br />
• Serial link<br />
• Can be programmed through its own keyboard<br />
• Real Time Clock (RTC)<br />
• Self tuning for each control loop, maximises efficiency<br />
for each loop<br />
The CZU is an Electronic Modulating Controller for the<br />
control of terminal units or fan coils in air conditioning<br />
systems serving small zones of buildings such as individual<br />
offices and hotel bedrooms.<br />
The range includes temperature sensors and actuators<br />
for valve operation and associated two, three and four<br />
port valves.<br />
FEATURES<br />
• Simple installation<br />
• Three wire connection to actuators<br />
• Optional auto changeover<br />
• Minimal commissioning time<br />
PRODUCT SELECTION<br />
19<br />
Control Range Output Power Supply<br />
MMC 4701 PID –40…+150°C 3 x 0...10Vdc 24vac<br />
0…100% rh 2 x 24V digital<br />
Data Sheet 2.701<br />
FEATURES<br />
• Serial link<br />
• Can be programmed through its own keyboard<br />
• Low voltage (24Vac)<br />
• Proportional + Integral + Derivative control action for stable control<br />
without offset<br />
• Eleven applications to deal with most humidity and temperature<br />
control schemes<br />
• Built-in real time clock and time schedule<br />
INSTALLATION DETAILS<br />
Power failure reserve - Settings stored in memory for 1 year, 5 year battery<br />
Inputs - Sensors: DRT, DDT, DOT, DRH, DDH, DOW, DOS, DWT<br />
Outputs - Actuators: ALi, ALE, ALES, AVUE<br />
24Vac switched outputs: 2 x digital outputs, ALX, ALXS, ARX<br />
Protection class - IP 40 when flush mounted<br />
Control Range Output Power Supply<br />
MMC 4601 Multi-loop –40…+150°C 2 x 0...10Vdc<br />
2 x 24V digital<br />
24Vac<br />
Data Sheet 2.751<br />
FEATURES (cont)<br />
• Fast response time ensures suitability for tap water control<br />
• Compensation curve can have up to three programmable points giving the<br />
curve two calculated ratios<br />
• Supply high limit<br />
• Built-in ‘default programme’ of typical settings for every parameter operates<br />
on initial start-up<br />
• 0...10Vdc control outputs<br />
• PID programmable control loops<br />
• Periodic pump cycling<br />
• Frost protection logic<br />
INSTALLATION DETAILS<br />
Power failure reserve - Settings stored in memory for 1 year, 5 year battery<br />
Inputs - Global sensors<br />
Outputs - Actuators: ALi, ALE, ALES, AVUE<br />
24Vac switched outputs: 2 x digital outputs<br />
Protection class - IP 40 when flush mounted<br />
Control Range Output<br />
CZU 4201 2-stage heating and<br />
cooling with dead zone<br />
10...40°C 24V actuator control<br />
Data Sheet 2.201<br />
INSTALLATION DETAILS<br />
Power supply - 24Vac (±10%) 50/60Hz<br />
Protection class - IP 20<br />
Override inputs - TSM 1501: Pipe surface thermostat<br />
Adjustments - Set Value: 10…40°C, Proportion Band: 0…3°K per stage<br />
Dead Zone: 0…6°K, Actuator Stroke Setting: 12.5…75mm<br />
Sensor inputs<br />
Type Range<br />
DRT 3451, 3453, 3801, 3851 Room –5...+40°C<br />
DDT 0001 Duct –5...+100°C<br />
DDU 0001, 1803 Duct –5...+40°C