<strong>Satchwell</strong> Controllers<br />

Keyboard<br />

MMC 4701<br />

Universal Air<br />

Handling Unit<br />

Controller<br />

MMC 4601<br />

Multi-loop District<br />

Heating Controller<br />

Terminal Unit<br />

CZU<br />

Fan Coil Unit<br />

Controller<br />

This PID Controller can be used to control humidity or<br />

temperature in various ventilation and air conditioning<br />

system applications.<br />

The serial link function allows the MMC to be fully<br />

integrated into a networking system with all the advantages<br />

of remote monitoring, alarms, logging, graphics and remote<br />

setting of all control parameters. The MMC can work as a<br />

fully stand-alone controller.<br />

The controller can be configured to run in one of the<br />

applications by simply selecting that application number.<br />

1. Single Stage Temperature Controller<br />

2. Two Stage Temperature Controller<br />

3. Three Stage Temperature Controller<br />

4. Three Stage Room Temperature Reset Controller with<br />

Heat Recovery<br />

5. Three Stage Cascade Temperature Controller<br />

6. Single Stage Temperature Controller<br />

(24Vac Actuator Output)<br />

7. Single Stage Humidity Controller<br />

8. Two Stage Humidity Controller<br />

9. Simple Single Stage Temperature Controller<br />

10. Simple Two Stage Temperature Controller<br />

11. Simple Three Stage Temperature Controller<br />

The MMC is a Multi-loop Controller for use in district<br />

heating schemes.<br />

The controller incorporates three separate control loops, two<br />

compensated and the other a constant temperature loop.<br />

Up to 3 specific points are programmed for the<br />

compensation graph. The MMC automatically joins up these<br />

points to produce a user defined compensation curve. This<br />

adjusts and calculates the required set value of the supply<br />

temperature to the compensated system to match the<br />

prevailing requirements.<br />

The MMC has a self tuning function that allows each of the<br />

3 control loops to have its proportional band, integral action<br />

and derivative action values automatically tuned. Self tuning<br />

can be carried out from the MMC keyboard or from<br />

optional external momentary switches connected to it. Self<br />

tuning maximises the efficiency of control loop operation.<br />

FEATURES<br />

• Serial link<br />

• Can be programmed through its own keyboard<br />

• Real Time Clock (RTC)<br />

• Self tuning for each control loop, maximises efficiency<br />

for each loop<br />

The CZU is an Electronic Modulating Controller for the<br />

control of terminal units or fan coils in air conditioning<br />

systems serving small zones of buildings such as individual<br />

offices and hotel bedrooms.<br />

The range includes temperature sensors and actuators<br />

for valve operation and associated two, three and four<br />

port valves.<br />

FEATURES<br />

• Simple installation<br />

• Three wire connection to actuators<br />

• Optional auto changeover<br />

• Minimal commissioning time<br />

PRODUCT SELECTION<br />

19<br />

Control Range Output Power Supply<br />

MMC 4701 PID –40…+150°C 3 x 0...10Vdc 24vac<br />

0…100% rh 2 x 24V digital<br />

Data Sheet 2.701<br />

FEATURES<br />

• Serial link<br />

• Can be programmed through its own keyboard<br />

• Low voltage (24Vac)<br />

• Proportional + Integral + Derivative control action for stable control<br />

without offset<br />

• Eleven applications to deal with most humidity and temperature<br />

control schemes<br />

• Built-in real time clock and time schedule<br />

INSTALLATION DETAILS<br />

Power failure reserve - Settings stored in memory for 1 year, 5 year battery<br />

Inputs - Sensors: DRT, DDT, DOT, DRH, DDH, DOW, DOS, DWT<br />

Outputs - Actuators: ALi, ALE, ALES, AVUE<br />

24Vac switched outputs: 2 x digital outputs, ALX, ALXS, ARX<br />

Protection class - IP 40 when flush mounted<br />

Control Range Output Power Supply<br />

MMC 4601 Multi-loop –40…+150°C 2 x 0...10Vdc<br />

2 x 24V digital<br />

24Vac<br />

Data Sheet 2.751<br />

FEATURES (cont)<br />

• Fast response time ensures suitability for tap water control<br />

• Compensation curve can have up to three programmable points giving the<br />

curve two calculated ratios<br />

• Supply high limit<br />

• Built-in ‘default programme’ of typical settings for every parameter operates<br />

on initial start-up<br />

• 0...10Vdc control outputs<br />

• PID programmable control loops<br />

• Periodic pump cycling<br />

• Frost protection logic<br />

INSTALLATION DETAILS<br />

Power failure reserve - Settings stored in memory for 1 year, 5 year battery<br />

Inputs - Global sensors<br />

Outputs - Actuators: ALi, ALE, ALES, AVUE<br />

24Vac switched outputs: 2 x digital outputs<br />

Protection class - IP 40 when flush mounted<br />

Control Range Output<br />

CZU 4201 2-stage heating and<br />

cooling with dead zone<br />

10...40°C 24V actuator control<br />

Data Sheet 2.201<br />

INSTALLATION DETAILS<br />

Power supply - 24Vac (±10%) 50/60Hz<br />

Protection class - IP 20<br />

Override inputs - TSM 1501: Pipe surface thermostat<br />

Adjustments - Set Value: 10…40°C, Proportion Band: 0…3°K per stage<br />

Dead Zone: 0…6°K, Actuator Stroke Setting: 12.5…75mm<br />

Sensor inputs<br />

Type Range<br />

DRT 3451, 3453, 3801, 3851 Room –5...+40°C<br />

DDT 0001 Duct –5...+100°C<br />

DDU 0001, 1803 Duct –5...+40°C