<strong>Satchwell</strong> Controllers/Sensors<br />

Intelligent/Programmable (cont)<br />

IAC 600<br />

Universal Multi-<br />

Loop Intelligent<br />

Advanced<br />

Controller<br />

Touchscreen<br />

for IAC 600<br />

Controller<br />

The IAC 600 is a Multi-loop Configurable Controller<br />

designed primarily for use in typical multi-loop situations<br />

such as air-conditioning systems and Central Plant<br />

Heating/Cooling Systems.<br />

The base unit’s 6 control loops are configurable and can be<br />

used, for instance, to control the pre-heater, the main duct<br />

temperature, humidity, and re-heat. One advantage of this<br />

integrated multi-loop controller is that the normal interlocks<br />

set up between discrete controllers on a typical system, are<br />

carried out internally by the controller, thus saving on<br />

external wiring. The IAC unit also has a clock and time<br />

schedules built-in which are used to switch plant control<br />

modules etc. the IAC includes full plant sequence control<br />

and rotation based on plant hours run to control Chillers<br />

and Boilers as required. The controller also includes a<br />

number of preset applications in the software to cater for<br />

typical control schemes.<br />

The Satchnet Bubbleland software is fully graphical. Setting<br />

and amending the IAC configurations involves selecting and<br />

joining the required modules using the mouse.<br />

FEATURES<br />

• Intelligent Multi-loop Controller – up to 6 PID<br />

control loops<br />

• Compensation and optimisation modules<br />

• Configured via Satchsoft Networking<br />

• Standard selectable applications built in to the<br />

controller<br />

This optional Touchscreen gives access to upto 31* IAC base<br />

units on its own sub LAN (including the IAC 600, 400, 420<br />

and 200). The Touchscreen is mounted direct on the IAC<br />

base unit.<br />

The Touchscreen allows the user to interrogate the IACs by<br />

using the touch sensitive screen and menu system.<br />

Information on the sensor values and outputs can be<br />

displayed and parameters can be altered if required. The<br />

Touchscreen contains a battery backed clock that is used<br />

by the IACs on the sub LAN as a back up to their own<br />

internal clocks.<br />

* Dependent on the number of parameters to be displayed.<br />

Each Touchscreen can display upto 256 parameters.<br />

FEATURES<br />

• Mounts on IAC base unit or optional panel mounting<br />

• Touch sensitive graphic LCD screen<br />

• Menu operation for interrogation and setting<br />

• Back-lit screen for easy viewing<br />

• Communicate with up to 31 - IACs<br />

• Battery backed clock provides time synchronisation<br />

21<br />

Control Range Outputs<br />

IAC 600-B 6 x PID loops –40…+150°C 4 x 0...10Vdc<br />

20…90% rh 8 x on/off triac<br />

250…9750 Ohms<br />

0…10,000 Lux<br />

1 x 15Vdc<br />

Data Sheet 2.951<br />

FEATURES (cont)<br />

• Six temperature (resistive) sensor inputs<br />

• Six 0...10Vdc inputs for humidity, pressure and velocity<br />

• Eight Voltage free switched inputs for use as alarms, Pulse counting etc<br />

• Proportional, Integral and Derivative control actions can be individually set on<br />

each controller module<br />

• Lighting and chiller/boiler Sequence control<br />

• <strong>Inter</strong>nal time clock and time schedules for plant and controller switching<br />

INSTALLATION DETAILS<br />

Power supply - 24Vac (±10%) 50/60Hz<br />

15 volt dc output - 30 mA max<br />

Power failure reserve - Non volatile RAM preserves memory for 10 years under<br />

normal conditions of use.<br />

Inputs - Sensors: Six temperature (resistive). Six 0...10 Volt dc, max input 10 Volts dc<br />

Digital input: Eight voltage free contacts, opto isolated. the inputs can be used for pulse<br />

counting, 0.5Hz max. They can also be used for alarms, overrides etc.<br />

Serial link: EIA standard RS422/485 half duplex opto isolated<br />

Outputs - Actuators: Four 0...10 Volt dc. Eight digital (triac on/off) outputs<br />

Protection class - IP 20<br />

Mounting - DIN rail or surface mounting<br />

Part number & item<br />

IAC-TS Touchscreen<br />

Data Sheet 2.951<br />

Room Temperature, Temperature/humidity & Carbon Dioxide Sensors<br />

DR/DRT<br />

Air Temperature<br />

Sensors<br />

DRT<br />

Room Temperature<br />

Sensors<br />

Designed for use with <strong>Satchwell</strong> controllers to<br />

provide temperature control of heating and air<br />

conditioning plant.<br />

FEATURES<br />

• Aesthetically pleasing case designs<br />

• Small physical size<br />

• Wide temperature sensing range<br />

• Simple wiring connections<br />

• Simple commissioning<br />

INSTALLATION DETAILS<br />

Sensing element - Negative temp. coefficient<br />

thermistor (0...10k ohm)<br />

Wiring - Low voltage dc, DRT - 2, 3 or 4 wire<br />

and DR - 2 wire<br />

Designed for use with controllers to provide<br />

temperature control of heating and air<br />

conditioning plant.<br />

FEATURES<br />

• Aesthetically pleasing case designs<br />

• Small physical size<br />

• Wide temperature sensing range<br />

• Simple wiring connections<br />

• Simple commissioning<br />

PRODUCT SELECTION<br />

INSTALLATION DETAILS<br />

Power supply - Powered from the IAC unit<br />

Power failure reserve - Non volatile RAM with built-in Real Time Clock gives 3 year<br />

back up of clock and memory under normal conditions of use.<br />

ACCESSORY DDC 2601 Remote Touchscreen Adaptor Kit<br />

For use with controller or controller actuator types<br />

Adjustable scale Sensing CZT CSC LIB MMC CZU KMC IAC SVT BAS<br />

(exposed) range CXR MN Sigma<br />

DR 3253 none –5...+40°C – – – – – – – • –<br />

DRT 3451 10...35°C –5...+40°C – • – – • – – – –<br />

DRT 3453 none –5...+40°C • • • • • • • – •<br />

DRT 3651 10...35°C –5...+40°C • – – • – • • – •<br />

DRT 3652 10...35°C + LED –5...+40°C – – – – – – • – –<br />

Data sheet 2.1<strong>05</strong> 2.021 2.041 2.701 2.201 2.120 2.951 2.001 13.341<br />

2.110 2.541 2.751 10.XXX 13.XXX<br />

Data Sheet 1.001<br />

ACCESSORIES<br />

837-1-203 DR/DRT Guard Kit - protects against impact and tampering<br />

837-1-352 DRT +/– Scale Converter – used to convert standard exposed adjustment types. Consists of<br />

just the sensor front cover. Suitable for DRT 3451 and 3651.<br />

For use with controller or controller actuator types<br />

Adjustable scale Sensing CZT CSC LIB MMC CZU KMC IAC SVT BAS<br />

(exposed) range CXR MN Sigma<br />

DRT 4453 none –5...+40°C • • • • • • • – •<br />

Data sheet 2.1<strong>05</strong> 2.021 2.041 2.701 2.201 2.120 2.951 2.001 13.341<br />

2.110 2.541 2.751 10.XXX 13.XXX<br />

Data Sheet 1.040<br />

INSTALLATION DETAILS<br />

Sensing element - Negative temp. coefficient thermistor (0...10k ohm)<br />

Wiring - Low voltage dc, DRT - 2, 3 or 4 wire