<strong>Satchwell</strong> Controllers/Sensors<br />
Intelligent/Programmable (cont)<br />
IAC 600<br />
Universal Multi-<br />
Loop Intelligent<br />
Advanced<br />
Controller<br />
Touchscreen<br />
for IAC 600<br />
Controller<br />
The IAC 600 is a Multi-loop Configurable Controller<br />
designed primarily for use in typical multi-loop situations<br />
such as air-conditioning systems and Central Plant<br />
Heating/Cooling Systems.<br />
The base unit’s 6 control loops are configurable and can be<br />
used, for instance, to control the pre-heater, the main duct<br />
temperature, humidity, and re-heat. One advantage of this<br />
integrated multi-loop controller is that the normal interlocks<br />
set up between discrete controllers on a typical system, are<br />
carried out internally by the controller, thus saving on<br />
external wiring. The IAC unit also has a clock and time<br />
schedules built-in which are used to switch plant control<br />
modules etc. the IAC includes full plant sequence control<br />
and rotation based on plant hours run to control Chillers<br />
and Boilers as required. The controller also includes a<br />
number of preset applications in the software to cater for<br />
typical control schemes.<br />
The Satchnet Bubbleland software is fully graphical. Setting<br />
and amending the IAC configurations involves selecting and<br />
joining the required modules using the mouse.<br />
FEATURES<br />
• Intelligent Multi-loop Controller – up to 6 PID<br />
control loops<br />
• Compensation and optimisation modules<br />
• Configured via Satchsoft Networking<br />
• Standard selectable applications built in to the<br />
controller<br />
This optional Touchscreen gives access to upto 31* IAC base<br />
units on its own sub LAN (including the IAC 600, 400, 420<br />
and 200). The Touchscreen is mounted direct on the IAC<br />
base unit.<br />
The Touchscreen allows the user to interrogate the IACs by<br />
using the touch sensitive screen and menu system.<br />
Information on the sensor values and outputs can be<br />
displayed and parameters can be altered if required. The<br />
Touchscreen contains a battery backed clock that is used<br />
by the IACs on the sub LAN as a back up to their own<br />
internal clocks.<br />
* Dependent on the number of parameters to be displayed.<br />
Each Touchscreen can display upto 256 parameters.<br />
FEATURES<br />
• Mounts on IAC base unit or optional panel mounting<br />
• Touch sensitive graphic LCD screen<br />
• Menu operation for interrogation and setting<br />
• Back-lit screen for easy viewing<br />
• Communicate with up to 31 - IACs<br />
• Battery backed clock provides time synchronisation<br />
21<br />
Control Range Outputs<br />
IAC 600-B 6 x PID loops –40…+150°C 4 x 0...10Vdc<br />
20…90% rh 8 x on/off triac<br />
250…9750 Ohms<br />
0…10,000 Lux<br />
1 x 15Vdc<br />
Data Sheet 2.951<br />
FEATURES (cont)<br />
• Six temperature (resistive) sensor inputs<br />
• Six 0...10Vdc inputs for humidity, pressure and velocity<br />
• Eight Voltage free switched inputs for use as alarms, Pulse counting etc<br />
• Proportional, Integral and Derivative control actions can be individually set on<br />
each controller module<br />
• Lighting and chiller/boiler Sequence control<br />
• <strong>Inter</strong>nal time clock and time schedules for plant and controller switching<br />
INSTALLATION DETAILS<br />
Power supply - 24Vac (±10%) 50/60Hz<br />
15 volt dc output - 30 mA max<br />
Power failure reserve - Non volatile RAM preserves memory for 10 years under<br />
normal conditions of use.<br />
Inputs - Sensors: Six temperature (resistive). Six 0...10 Volt dc, max input 10 Volts dc<br />
Digital input: Eight voltage free contacts, opto isolated. the inputs can be used for pulse<br />
counting, 0.5Hz max. They can also be used for alarms, overrides etc.<br />
Serial link: EIA standard RS422/485 half duplex opto isolated<br />
Outputs - Actuators: Four 0...10 Volt dc. Eight digital (triac on/off) outputs<br />
Protection class - IP 20<br />
Mounting - DIN rail or surface mounting<br />
Part number & item<br />
IAC-TS Touchscreen<br />
Data Sheet 2.951<br />
Room Temperature, Temperature/humidity & Carbon Dioxide Sensors<br />
DR/DRT<br />
Air Temperature<br />
Sensors<br />
DRT<br />
Room Temperature<br />
Sensors<br />
Designed for use with <strong>Satchwell</strong> controllers to<br />
provide temperature control of heating and air<br />
conditioning plant.<br />
FEATURES<br />
• Aesthetically pleasing case designs<br />
• Small physical size<br />
• Wide temperature sensing range<br />
• Simple wiring connections<br />
• Simple commissioning<br />
INSTALLATION DETAILS<br />
Sensing element - Negative temp. coefficient<br />
thermistor (0...10k ohm)<br />
Wiring - Low voltage dc, DRT - 2, 3 or 4 wire<br />
and DR - 2 wire<br />
Designed for use with controllers to provide<br />
temperature control of heating and air<br />
conditioning plant.<br />
FEATURES<br />
• Aesthetically pleasing case designs<br />
• Small physical size<br />
• Wide temperature sensing range<br />
• Simple wiring connections<br />
• Simple commissioning<br />
PRODUCT SELECTION<br />
INSTALLATION DETAILS<br />
Power supply - Powered from the IAC unit<br />
Power failure reserve - Non volatile RAM with built-in Real Time Clock gives 3 year<br />
back up of clock and memory under normal conditions of use.<br />
ACCESSORY DDC 2601 Remote Touchscreen Adaptor Kit<br />
For use with controller or controller actuator types<br />
Adjustable scale Sensing CZT CSC LIB MMC CZU KMC IAC SVT BAS<br />
(exposed) range CXR MN Sigma<br />
DR 3253 none –5...+40°C – – – – – – – • –<br />
DRT 3451 10...35°C –5...+40°C – • – – • – – – –<br />
DRT 3453 none –5...+40°C • • • • • • • – •<br />
DRT 3651 10...35°C –5...+40°C • – – • – • • – •<br />
DRT 3652 10...35°C + LED –5...+40°C – – – – – – • – –<br />
Data sheet 2.1<strong>05</strong> 2.021 2.041 2.701 2.201 2.120 2.951 2.001 13.341<br />
2.110 2.541 2.751 10.XXX 13.XXX<br />
Data Sheet 1.001<br />
ACCESSORIES<br />
837-1-203 DR/DRT Guard Kit - protects against impact and tampering<br />
837-1-352 DRT +/– Scale Converter – used to convert standard exposed adjustment types. Consists of<br />
just the sensor front cover. Suitable for DRT 3451 and 3651.<br />
For use with controller or controller actuator types<br />
Adjustable scale Sensing CZT CSC LIB MMC CZU KMC IAC SVT BAS<br />
(exposed) range CXR MN Sigma<br />
DRT 4453 none –5...+40°C • • • • • • • – •<br />
Data sheet 2.1<strong>05</strong> 2.021 2.041 2.701 2.201 2.120 2.951 2.001 13.341<br />
2.110 2.541 2.751 10.XXX 13.XXX<br />
Data Sheet 1.040<br />
INSTALLATION DETAILS<br />
Sensing element - Negative temp. coefficient thermistor (0...10k ohm)<br />
Wiring - Low voltage dc, DRT - 2, 3 or 4 wire