Networking<br />

MIU<br />

Modem <strong>Inter</strong>face<br />

Unit<br />

Intelligent/Programmable<br />

IAC 420<br />

Universal Multi-<br />

Loop Intelligent<br />

Advanced<br />

Controller<br />

The Modem <strong>Inter</strong>face Unit provides the necessary link<br />

between a modem and <strong>Satchwell</strong> Networking controllers on<br />

a remote site, when using Satchnet Pro Networking<br />

Software. An RS232 input is provided for connection to a<br />

modem on a Wide Area Network (WAN). The MIU is then<br />

able to be connected (via its RS422/485 link) to upto 31<br />

Networking controllers.<br />

FEATURES<br />

• RS232 and RS422/485 ports<br />

• Autoanswer operation on modem sites<br />

• Optional battery backed up Real Time Clock Board<br />

• Allows a further 32 Networking controllers to be<br />

connected, making a maximum of 63 on a single LAN<br />

This Intelligent Advanced Controller is designed for use in<br />

small and large buildings such as office blocks, hotels and<br />

schools. The IAC has a stand alone capability, and may be<br />

configured from a central computer over the serial link.<br />

The IAC has pre-sets to control common applications such as<br />

terminal unit control, VAV and zone control. In addition the<br />

controller can be customised to work on other less common<br />

applications.<br />

The Satchnet software is used to program and monitor the<br />

IAC controllers.<br />

FEATURES<br />

• Compact size allows mounting in a confined space<br />

such as on a fan coil unit<br />

• Serial link<br />

• IACs configured from a computer using the simple<br />

Bubbleland graphical interface<br />

• <strong>Inter</strong>nal software time clock, controller and lighting<br />

time schedules<br />

• Complies with latest European EMC standards<br />

• Switched outputs may be configured as stepped<br />

outputs (including plant rotation), actuator outputs or<br />

outputs for lights and fans<br />

• Six configurable inputs that can be individually<br />

configured as temperature (resistive), analogue<br />

(0...10Vdc) or Digital (Switched) inputs<br />

• 0...10 volt inputs can be used for<br />

humidity/pressure/velocity control or as a reset input<br />

• Resistive inputs can be used for <strong>Satchwell</strong> “T” type<br />

temperature sensors, RPW remote setting units,<br />

Ohms and Light sensors (NORP-12 Light Dependent<br />

Resistor (LDR)).<br />

PRODUCT SELECTION <strong>Satchwell</strong> Controllers<br />

20<br />

Comms. ports Max. cable<br />

Comms. speed length<br />

MIU 4252 1 - RS232<br />

1200, 2400, 4800 or 9600 BPS<br />

15m<br />

2 - RS422/485<br />

1200, 2400, 4800 or 9600 BPS<br />

(opto isolated)<br />

1000m<br />

Data Sheet 2.511<br />

INSTALLATION DETAILS<br />

Power supply - 24Vac (±15%) 47/63Hz<br />

Protection class - IP 41, IP 00 if the RS232 connected is used<br />

Mounting - DIN rail or surface mounting<br />

Status display - 5 LEDs<br />

Power failure reserve - E 2 PROM preserves configuration data such as password,<br />

telephone numbers, baud rate (if LK 5 is not used) etc.<br />

ACCESSORY 841-2-201 Real Time Clock Board<br />

Terminals Control Range Outputs<br />

IAC 420 - F Fixed 3 loop –40…+150°C 3 x 0...10Vdc<br />

IAC 420 - P Plug-in 20…90% rh 3 x 24V pulsed<br />

250…9750 Ohms 24V switched<br />

0…10,000 Lux 1 x 15Vdc<br />

Data Sheet 2.801<br />

FEATURES (cont)<br />

• 15Vdc supply output for humidity, pressure and UniFact sensors<br />

• 0...10Vdc or stepped fan control<br />

• Averaging of temperature (resistive) sensors and analogue inputs<br />

• Three off two stage controllers with each stage individually selected as PID,<br />

PI or P only<br />

• Three cascade controllers<br />

• Optional Real Time Clock (RTC) board available<br />

INSTALLATION DETAILS<br />

Power supply - 24Vac (±10%) 47/63Hz<br />

15 Volt dc Output - 25 mA max<br />

Power failure reserve - E 2 PROM preserves configuration data and user settings.<br />

Inputs: 6 x configurable inputs<br />

Outputs: 3 x 0...10V outputs, 6 x digital (triacs on/off) outputs<br />

Protection class - IP 20<br />

Mounting - DIN rail or surface mounting<br />

ACCESSORY 841-1-201 Real Time Clock Board