Networking<br />
MIU<br />
Modem <strong>Inter</strong>face<br />
Unit<br />
Intelligent/Programmable<br />
IAC 420<br />
Universal Multi-<br />
Loop Intelligent<br />
Advanced<br />
Controller<br />
The Modem <strong>Inter</strong>face Unit provides the necessary link<br />
between a modem and <strong>Satchwell</strong> Networking controllers on<br />
a remote site, when using Satchnet Pro Networking<br />
Software. An RS232 input is provided for connection to a<br />
modem on a Wide Area Network (WAN). The MIU is then<br />
able to be connected (via its RS422/485 link) to upto 31<br />
Networking controllers.<br />
FEATURES<br />
• RS232 and RS422/485 ports<br />
• Autoanswer operation on modem sites<br />
• Optional battery backed up Real Time Clock Board<br />
• Allows a further 32 Networking controllers to be<br />
connected, making a maximum of 63 on a single LAN<br />
This Intelligent Advanced Controller is designed for use in<br />
small and large buildings such as office blocks, hotels and<br />
schools. The IAC has a stand alone capability, and may be<br />
configured from a central computer over the serial link.<br />
The IAC has pre-sets to control common applications such as<br />
terminal unit control, VAV and zone control. In addition the<br />
controller can be customised to work on other less common<br />
applications.<br />
The Satchnet software is used to program and monitor the<br />
IAC controllers.<br />
FEATURES<br />
• Compact size allows mounting in a confined space<br />
such as on a fan coil unit<br />
• Serial link<br />
• IACs configured from a computer using the simple<br />
Bubbleland graphical interface<br />
• <strong>Inter</strong>nal software time clock, controller and lighting<br />
time schedules<br />
• Complies with latest European EMC standards<br />
• Switched outputs may be configured as stepped<br />
outputs (including plant rotation), actuator outputs or<br />
outputs for lights and fans<br />
• Six configurable inputs that can be individually<br />
configured as temperature (resistive), analogue<br />
(0...10Vdc) or Digital (Switched) inputs<br />
• 0...10 volt inputs can be used for<br />
humidity/pressure/velocity control or as a reset input<br />
• Resistive inputs can be used for <strong>Satchwell</strong> “T” type<br />
temperature sensors, RPW remote setting units,<br />
Ohms and Light sensors (NORP-12 Light Dependent<br />
Resistor (LDR)).<br />
PRODUCT SELECTION <strong>Satchwell</strong> Controllers<br />
20<br />
Comms. ports Max. cable<br />
Comms. speed length<br />
MIU 4252 1 - RS232<br />
1200, 2400, 4800 or 9600 BPS<br />
15m<br />
2 - RS422/485<br />
1200, 2400, 4800 or 9600 BPS<br />
(opto isolated)<br />
1000m<br />
Data Sheet 2.511<br />
INSTALLATION DETAILS<br />
Power supply - 24Vac (±15%) 47/63Hz<br />
Protection class - IP 41, IP 00 if the RS232 connected is used<br />
Mounting - DIN rail or surface mounting<br />
Status display - 5 LEDs<br />
Power failure reserve - E 2 PROM preserves configuration data such as password,<br />
telephone numbers, baud rate (if LK 5 is not used) etc.<br />
ACCESSORY 841-2-201 Real Time Clock Board<br />
Terminals Control Range Outputs<br />
IAC 420 - F Fixed 3 loop –40…+150°C 3 x 0...10Vdc<br />
IAC 420 - P Plug-in 20…90% rh 3 x 24V pulsed<br />
250…9750 Ohms 24V switched<br />
0…10,000 Lux 1 x 15Vdc<br />
Data Sheet 2.801<br />
FEATURES (cont)<br />
• 15Vdc supply output for humidity, pressure and UniFact sensors<br />
• 0...10Vdc or stepped fan control<br />
• Averaging of temperature (resistive) sensors and analogue inputs<br />
• Three off two stage controllers with each stage individually selected as PID,<br />
PI or P only<br />
• Three cascade controllers<br />
• Optional Real Time Clock (RTC) board available<br />
INSTALLATION DETAILS<br />
Power supply - 24Vac (±10%) 47/63Hz<br />
15 Volt dc Output - 25 mA max<br />
Power failure reserve - E 2 PROM preserves configuration data and user settings.<br />
Inputs: 6 x configurable inputs<br />
Outputs: 3 x 0...10V outputs, 6 x digital (triacs on/off) outputs<br />
Protection class - IP 20<br />
Mounting - DIN rail or surface mounting<br />