<strong>Satchwell</strong> MicroNet<br />
Controllers (LONMARK ® ) (cont)<br />
MN VAV<br />
Controller only<br />
Accessories<br />
for MicroNet<br />
LONMARk Controllers<br />
Controllers (Bus-du-jour ® )<br />
MN 300<br />
Programmable<br />
Bus-du-jour ®<br />
Controller<br />
MN 440<br />
Programmable<br />
Bus-du-jour ®<br />
Controller<br />
The MicroNet VAV Series (Variable Air Volume)<br />
Controller is an interoperable, LONMARKcompliant<br />
device. When loaded with an<br />
application from the WorkPlace Tech Tool<br />
application library or programmed with the<br />
WorkPlace Tech Tool, it provides control<br />
strategies for pressure independent terminal<br />
boxes, with or without reheat capabilities.<br />
FEATURES<br />
• LONMARK compliant, programmable<br />
• Proportional (P), Proportional Plus Integral (PI), and<br />
Proportional Plus Integral and Derivative (PID) control<br />
for cooling and heating<br />
• Plenum-rated enclosure<br />
• Air balancing using the MicroNet VAV Flow<br />
Balance software<br />
• Directly compatible with terminal boxes which contain<br />
a synchronous-motor-driven damper actuator<br />
INSTALLATION DETAILS<br />
Power supply - 20.4...30Vac, 50/60Hz<br />
Consumption - 102VA max: 12VA plus DO loads (24VA<br />
each) and triac load (total 18VA)<br />
Surge immunity compliance - IEC 1000-4-5. ANSI C62.41<br />
(IEEE-587, Category A & B)<br />
PRODUCT SELECTION<br />
AD-8961-220 Voltage Divider (converts 1...11Vdc signal to 0.45...5Vdc signal) for universal inputs<br />
AD-8969-202 250Ω Shunt Resistor Kit for 4...20mA universal inputs<br />
LON-TERM1 Single LON Terminator for Free Topologies<br />
LON-TERM2 Double LON Terminator for Bus Topologies (two required)<br />
MN Sx MicroNet Digital Sensors<br />
WPA-LON-1 PC ISA Card (16-bit) to connect PCs to LONWORKS FTT-10 network<br />
WPA-LON-2 PCMCIA Card to connect Laptop PCs to LONWORKS FTT-10 network<br />
ECH-74401 PCLTA_20/FT-10 PCI 932-bit) Desktop <strong>Inter</strong>face<br />
WP-TECH-CD-E-32 WorkPlace Tech Tool<br />
WP-TECH-32 WorkPlace Tech Tool Unlock Codes<br />
The MN 300 controller is designed for unitary control,<br />
boilers and special applications that may require built-in<br />
transformers and relays.<br />
The controller can function in stand-alone mode or as part<br />
of a networked system using Bus-du-jour communication<br />
options.<br />
FEATURES<br />
• LONWORKS FTT-10, ARCNET and NCP communications<br />
options - Bus-du-jour<br />
• Fully programmable using graphical objects<br />
• Three built-in 230Vac relays<br />
• 230Vac or 24Vac power supply combined with<br />
compact size<br />
• Time schedules<br />
• Switched outputs may be configured as stepped<br />
outputs (including plant rotation), actuator outputs<br />
or outputs for lights and fans<br />
• Eight fully programmable inputs - digital, analogue<br />
0...10V, resistive 0...10Ω<br />
This controller is designed for rooftop, unit vent, air<br />
handling unit (AHU), and central heating and cooling<br />
applications.<br />
The controller can function in stand-alone mode or as part<br />
of a networked system using Bus-du-jour communication<br />
options. An optional Real Time Clock Card can be fitted to<br />
the MN 440 on an NCP network.<br />
FEATURES<br />
• LONWORKS FTT-10, ARCNET and NCP communications<br />
options - Bus-du-jour concept<br />
• Fully programmable using graphical objects<br />
• Intelligent multi-loop controller - up to 7 PID<br />
control loops<br />
• Time schedules<br />
• Proportional, integral and derivative control actions<br />
• 0...10Vdc for stepped fan control<br />
• Averaging module for analogue inputs<br />
• Six easily configurable inputs - digital, analogue<br />
0...10V, resistive 0...10kΩ<br />
9<br />
Controller Control Inputs/outputs Reheat type Other<br />
MNL-V3RV2 with fan Cooling, 1 x digital input (DI) Staged electric, Occupancy<br />
and/or series 1 x universal input (UI) floating/proportional satellite<br />
reheat induction, 3 x digital outputs (DO) hydronic,<br />
control<br />
Data Sheet 10.121<br />
parallel fan 1 x analogue output (AO) time Proportioned<br />
2 x triac outputs (TO)<br />
INSTALLATION DETAILS (cont)<br />
Velocity pressure input - Operating range: 0.0...2.5” of W.C. (0.0...0.622kPa)<br />
Control range: 0.01...2.00” of W.C. (0.0025...0.498kPa)<br />
Accuracy: ±5% @ 1.00” of W.C. (0.249kPa) with Laminar flow @ 77°F (25°C) and<br />
suitable flow station<br />
Protection class - IP 20<br />
Sensor inputs - MN Sx digital sensor link<br />
Digital outputs - Relay: SW24H1, 2 & 3 current ratings 24VA each @ 24Vac, 50/60Hz<br />
Triac: current ratings 0.75A (18VA) each output at 24Vac. Total of 18VA for both outputs<br />
Typical load: 24Vac synchronous motor with impedance protected windings<br />
Digital input - Input type: Dry contact<br />
Universal input - 10k thermistor input, voltage, current, digital input<br />
Analogue output - Current 0...20mA (output load from 80...550Ω).<br />
ACCESSORIES – and see below<br />
MNA-FLO-1 MicroNet VAV Enclosure for conduit applications<br />
MNL-FLOW-BAL MicroNet Flow Balance Software<br />
Controller Comms protocol Inputs/outputs<br />
MNN-30-100 NCP Controller NCP as standard 8 x universal inputs<br />
ARCNET with plug-in card 4 x triac outputs<br />
LONWORKS with plug-in card 3 x relay outputs<br />
Data Sheet 10.101<br />
INSTALLATION DETAILS<br />
Power supply - 24Vac or 230Vac, 50/60Hz<br />
Consumption - 12VA<br />
Protection class - IP 20<br />
Mounting - Wall or 35mm DIN rail<br />
Sensor inputs - MN Sx digital sensor link<br />
Inputs - 8 universal inputs (digital, resistive, 0...10Vdc)<br />
Outputs - 4 triac outputs for switching 24Vac<br />
3 SPDT 230Vac relays (Line Relays)<br />
Current ratings (for triac outputs): 6Va at 230Vac supply, 18VA at 24Vac supply<br />
Power failure reserve - Controller EEPROM preserves memory for 10 years under<br />
normal conditions of use. The software clock will stop during a power failure. However,<br />
if the controller has an RTC card, the time will not be lost.<br />
ACCESSORIES – see page 10<br />
Controller Comms protocol Inputs/outputs<br />
MNN-44-100 NCP NCP as standard 6 x universal inputs<br />
Programmable ARCNET with plug-in card 6 x digital outputs<br />
Controller LONWORKS with plug-in card 3 x analogue outputs<br />
Data Sheet 10.102<br />
INSTALLATION DETAILS<br />
Power supply - 24Vac, 50/60Hz<br />
Consumption - 10VA<br />
Protection class - IP 20<br />
Mounting - Wall or 35mm DIN rail<br />
Inputs - 6 universal inputs (digital, resistive, 0...10Vdc)<br />
Outputs - 6 digital outputs (triac) for switching 24Vac<br />
3 analogue outputs (0...10Vdc)<br />
Current ratings for triacs: 18VA at 24Vac.<br />
Also has a 15Vdc power supply output capable of sourcing 25mA<br />
Power failure reserve - Controller EEPROM preserves memory for 10 years under<br />
normal conditions of use. The software clock will stop during a power failure. However,<br />
if the controller has an RTC card, the time will not be lost.<br />
ACCESSORIES – see page 10