38059-Satchwell Inter. Guide 05
38059-Satchwell Inter. Guide 05
38059-Satchwell Inter. Guide 05
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Room Temperature, Temperature/humidity & Carbon Dioxide Sensors (cont)<br />
DRT<br />
Temperature<br />
Sensors with Fan<br />
Speed Switches<br />
DU, DUS<br />
DUSF<br />
MicroNet Sensors<br />
DRTE<br />
Active Temperature<br />
Sensor<br />
DRTE<br />
Active Temperature<br />
Sensors with Fan<br />
Speed Switches<br />
DRH, DRTH<br />
Room Humidity/<br />
Temperature<br />
Sensors<br />
Sensors incorporate fan speed control switches and are used<br />
with CZU and IAC temperature controllers. This system is<br />
used for the control of temperature zones in buildings, such<br />
as hotel bedrooms or individual offices, which are air<br />
conditioned by fan coil units.<br />
FEATURES<br />
• Aesthetically pleasing case designs<br />
• Robust<br />
• Easy to operate<br />
• Simple wiring connections<br />
• Simple commissioning<br />
These sensors are specifically used for <strong>Satchwell</strong> controllers.<br />
Models types have light that informs you that the controller<br />
is running. All sensors use the same single gang sized case.<br />
FEATURES<br />
• Small physical size<br />
• Attractive case design and neutral colour fits in with<br />
most room designs<br />
• Extra low voltage on all sensor types including fan<br />
speed control versions<br />
• Simple wiring connections<br />
• Simple commissioning<br />
• Controller running power light on the sensor<br />
The DRTE Active Sensor gives proportional 0...10Vdc output<br />
for control of rooms or small zones. The sensor will control<br />
actuators such as <strong>Satchwell</strong> ALi and ARE. Alternately the<br />
output can be used as a low limit on other 10 volt<br />
equipment or as a reset signal to other controllers.<br />
FEATURES<br />
• Tamperproof<br />
• Small physical size<br />
• Reversible output ramp: heating or cooling<br />
• Low cost installation<br />
• Simple commissioning<br />
Sensors incorporate fan speed control switches. These<br />
devices are used for the control of temperature zones in<br />
buildings, such as hotel bedrooms or individual offices,<br />
which are air conditioned by fan coil units. Can be used with<br />
any 0...10V actuator.<br />
INSTALLATION DETAILS<br />
Sensing element - Negative temp. coefficient thermistor<br />
Switch rating - 2.5A 250Vac. Motor full load current. 12A<br />
motor starting, 250Vac. Note: manual switches suitable for<br />
choke controlled or capacitor controlled fan motors.<br />
This sensor range is designed for use with controllers to<br />
provide relative humidity measurement and temperature<br />
control in ventilation systems.<br />
Models are available with humidity sensing only or humidity<br />
combined with temperature sensing. Two ranges of resistive<br />
outputs are available across the monitored temperature<br />
range i.e. T type or standard NTC thermistor. 2% and 1%<br />
accuracy versions are available certified for the National<br />
Institute of Standards Technology (NIST).<br />
FEATURES<br />
• Aesthetically styled, low profile packaging<br />
• 0...10Vdc humidity output<br />
• 24Vac or 12...24Vdc input power<br />
• Humidity or humidity and temperature output<br />
• Removable Humidity sensor element; replacement<br />
elements available<br />
• 1% and 2% versions supplied with NIST certificate<br />
PRODUCT SELECTION <strong>Satchwell</strong> Sensors<br />
22<br />
Adjustable Sensing No. switch Switch Switch<br />
scale range positions position function<br />
DRT 3801 10...35°C 10...35°C 2 0, 1 Off, on<br />
DRT 3851 10...35°C 10...35°C 4 0, 1, 2, 3 Off, on, medium, high<br />
Data Sheet 1.002<br />
Associated controllers: CZU, IAC<br />
INSTALLATION DETAILS<br />
Sensing element - Negative temp. coefficient thermistor<br />
Wiring - 2 wire low voltage dc, non-polarised to controller<br />
Switch rating - 2.5A 250Vac. Motor full load current. 12A motor starting, 250Vac. Note:<br />
manual switches suitable for choke controlled or capacitor controlled fan motors.<br />
Adjustable Sensing Fan speed Switch<br />
scale range override function<br />
DU 4301 none –5...+50°C – –<br />
DUS 4302 +/– –5...+50°C – –<br />
DUSF 4351 +/– –5...+50°C • Auto, off, on<br />
DUSF 4352 +/– –5...+50°C • Auto, off, 1, 2, 3<br />
Data Sheet 1.020 Associated controllers: MN 200/440/500/620 (DU & DUS only URC)<br />
INSTALLATION DETAILS<br />
Sensing element - Negative temp. coefficient thermistor<br />
Wiring - Low voltage dc (15Vdc), DU 3 wire, DUS 4 wire, DUSF 7 wire<br />
Power supply - 15Vdc from UniFact controller<br />
ACCESSORY 837-1-203 Guard Kit<br />
Adjustable scale Sensing range<br />
DRTE 2201 none 0...40°C<br />
Data Sheet 1.101 Associated controllers: MMC and IAC (reset or low limit)<br />
Associated actuators: ALE, ALES, ARE, ARES, AVE, AVUE, ALi<br />
INSTALLATION DETAILS<br />
Sensing element - Negative temp. coefficient thermistor<br />
Output - 1 reversible 0...10Vdc signal (heating or cooling), 1 fixed 10Vdc output.<br />
Proportional band - 2...15K<br />
Power supply - 24Vac (+/–10%) 50/60Hz<br />
Protection class - IP 20<br />
Adjustable Sensing No.switch Switch Switch<br />
scale range positions position function<br />
DRTE 2801 10...40°C 10...35°C 2 0, 1 Off, on<br />
DRTE 2851 10...40°C 10...35°C 4 0, 1, 2, 3 Off, on, medium, high<br />
Data Sheet 1.102<br />
Associated actuators: ALE, ALES, ARE, ARES, AVE, AVUE, ALi<br />
Sensing Accuracy Temp. sensor Control range<br />
DRH 7702 Relative humidity only ±2% rh* None 0...90% rh<br />
DRH 7703 “ ±3% rh* and 0...+50°C<br />
DRTH 7712 Relative humidity and temp. ±2% rh* T type<br />
DRTH 7713 “ ±3% rh*<br />
DRTH 8731 “ ±1% rh** 0...10Vdc<br />
Data Sheet 1.502/1.504 *@10...90% rh **NIST Certified<br />
INSTALLATION DETAILS<br />
Power supply - 24Vac or 12...24Vdc for humidity sensors<br />
Humidity sensor - Digitally profiled thin-film capacitive element<br />
Temperature effect - ±0.03% rh/°C over 0...50°C<br />
Stability - ±1% rh annually at 20°C<br />
Protection class - IP 20<br />
Ambient limits - Operating temperature 0...60°C, humidity 10...90% rh, non-condensing<br />
Compatible controllers - KMC, MMC, IAC, MicroNet, BAS, Sigma<br />
ACCESSORIES<br />
HDS 9201 1% Humidity Element (NIST Certified)<br />
HDS 9202 2% Humidity Element (NIST Certified)<br />
HDS 9102 Replacement Humidity Element (2%)<br />
HDS 9103 Replacement Humidity Element (3%)<br />
Humidity: 0...90% rh<br />
and 0...+50°C<br />
Temperature 0...+100°C