Room Temperature, Temperature/humidity & Carbon Dioxide Sensors (cont)<br />

DRT<br />

Temperature<br />

Sensors with Fan<br />

Speed Switches<br />

DU, DUS<br />

DUSF<br />

MicroNet Sensors<br />

DRTE<br />

Active Temperature<br />

Sensor<br />

DRTE<br />

Active Temperature<br />

Sensors with Fan<br />

Speed Switches<br />

DRH, DRTH<br />

Room Humidity/<br />

Temperature<br />

Sensors<br />

Sensors incorporate fan speed control switches and are used<br />

with CZU and IAC temperature controllers. This system is<br />

used for the control of temperature zones in buildings, such<br />

as hotel bedrooms or individual offices, which are air<br />

conditioned by fan coil units.<br />

FEATURES<br />

• Aesthetically pleasing case designs<br />

• Robust<br />

• Easy to operate<br />

• Simple wiring connections<br />

• Simple commissioning<br />

These sensors are specifically used for <strong>Satchwell</strong> controllers.<br />

Models types have light that informs you that the controller<br />

is running. All sensors use the same single gang sized case.<br />

FEATURES<br />

• Small physical size<br />

• Attractive case design and neutral colour fits in with<br />

most room designs<br />

• Extra low voltage on all sensor types including fan<br />

speed control versions<br />

• Simple wiring connections<br />

• Simple commissioning<br />

• Controller running power light on the sensor<br />

The DRTE Active Sensor gives proportional 0...10Vdc output<br />

for control of rooms or small zones. The sensor will control<br />

actuators such as <strong>Satchwell</strong> ALi and ARE. Alternately the<br />

output can be used as a low limit on other 10 volt<br />

equipment or as a reset signal to other controllers.<br />

FEATURES<br />

• Tamperproof<br />

• Small physical size<br />

• Reversible output ramp: heating or cooling<br />

• Low cost installation<br />

• Simple commissioning<br />

Sensors incorporate fan speed control switches. These<br />

devices are used for the control of temperature zones in<br />

buildings, such as hotel bedrooms or individual offices,<br />

which are air conditioned by fan coil units. Can be used with<br />

any 0...10V actuator.<br />

INSTALLATION DETAILS<br />

Sensing element - Negative temp. coefficient thermistor<br />

Switch rating - 2.5A 250Vac. Motor full load current. 12A<br />

motor starting, 250Vac. Note: manual switches suitable for<br />

choke controlled or capacitor controlled fan motors.<br />

This sensor range is designed for use with controllers to<br />

provide relative humidity measurement and temperature<br />

control in ventilation systems.<br />

Models are available with humidity sensing only or humidity<br />

combined with temperature sensing. Two ranges of resistive<br />

outputs are available across the monitored temperature<br />

range i.e. T type or standard NTC thermistor. 2% and 1%<br />

accuracy versions are available certified for the National<br />

Institute of Standards Technology (NIST).<br />

FEATURES<br />

• Aesthetically styled, low profile packaging<br />

• 0...10Vdc humidity output<br />

• 24Vac or 12...24Vdc input power<br />

• Humidity or humidity and temperature output<br />

• Removable Humidity sensor element; replacement<br />

elements available<br />

• 1% and 2% versions supplied with NIST certificate<br />

PRODUCT SELECTION <strong>Satchwell</strong> Sensors<br />

22<br />

Adjustable Sensing No. switch Switch Switch<br />

scale range positions position function<br />

DRT 3801 10...35°C 10...35°C 2 0, 1 Off, on<br />

DRT 3851 10...35°C 10...35°C 4 0, 1, 2, 3 Off, on, medium, high<br />

Data Sheet 1.002<br />

Associated controllers: CZU, IAC<br />

INSTALLATION DETAILS<br />

Sensing element - Negative temp. coefficient thermistor<br />

Wiring - 2 wire low voltage dc, non-polarised to controller<br />

Switch rating - 2.5A 250Vac. Motor full load current. 12A motor starting, 250Vac. Note:<br />

manual switches suitable for choke controlled or capacitor controlled fan motors.<br />

Adjustable Sensing Fan speed Switch<br />

scale range override function<br />

DU 4301 none –5...+50°C – –<br />

DUS 4302 +/– –5...+50°C – –<br />

DUSF 4351 +/– –5...+50°C • Auto, off, on<br />

DUSF 4352 +/– –5...+50°C • Auto, off, 1, 2, 3<br />

Data Sheet 1.020 Associated controllers: MN 200/440/500/620 (DU & DUS only URC)<br />

INSTALLATION DETAILS<br />

Sensing element - Negative temp. coefficient thermistor<br />

Wiring - Low voltage dc (15Vdc), DU 3 wire, DUS 4 wire, DUSF 7 wire<br />

Power supply - 15Vdc from UniFact controller<br />

ACCESSORY 837-1-203 Guard Kit<br />

Adjustable scale Sensing range<br />

DRTE 2201 none 0...40°C<br />

Data Sheet 1.101 Associated controllers: MMC and IAC (reset or low limit)<br />

Associated actuators: ALE, ALES, ARE, ARES, AVE, AVUE, ALi<br />

INSTALLATION DETAILS<br />

Sensing element - Negative temp. coefficient thermistor<br />

Output - 1 reversible 0...10Vdc signal (heating or cooling), 1 fixed 10Vdc output.<br />

Proportional band - 2...15K<br />

Power supply - 24Vac (+/–10%) 50/60Hz<br />

Protection class - IP 20<br />

Adjustable Sensing No.switch Switch Switch<br />

scale range positions position function<br />

DRTE 2801 10...40°C 10...35°C 2 0, 1 Off, on<br />

DRTE 2851 10...40°C 10...35°C 4 0, 1, 2, 3 Off, on, medium, high<br />

Data Sheet 1.102<br />

Associated actuators: ALE, ALES, ARE, ARES, AVE, AVUE, ALi<br />

Sensing Accuracy Temp. sensor Control range<br />

DRH 7702 Relative humidity only ±2% rh* None 0...90% rh<br />

DRH 7703 “ ±3% rh* and 0...+50°C<br />

DRTH 7712 Relative humidity and temp. ±2% rh* T type<br />

DRTH 7713 “ ±3% rh*<br />

DRTH 8731 “ ±1% rh** 0...10Vdc<br />

Data Sheet 1.502/1.504 *@10...90% rh **NIST Certified<br />

INSTALLATION DETAILS<br />

Power supply - 24Vac or 12...24Vdc for humidity sensors<br />

Humidity sensor - Digitally profiled thin-film capacitive element<br />

Temperature effect - ±0.03% rh/°C over 0...50°C<br />

Stability - ±1% rh annually at 20°C<br />

Protection class - IP 20<br />

Ambient limits - Operating temperature 0...60°C, humidity 10...90% rh, non-condensing<br />

Compatible controllers - KMC, MMC, IAC, MicroNet, BAS, Sigma<br />

ACCESSORIES<br />

HDS 9201 1% Humidity Element (NIST Certified)<br />

HDS 9202 2% Humidity Element (NIST Certified)<br />

HDS 9102 Replacement Humidity Element (2%)<br />

HDS 9103 Replacement Humidity Element (3%)<br />

Humidity: 0...90% rh<br />

and 0...+50°C<br />

Temperature 0...+100°C