VENTILATION<br />
ON / OFF (Start & Stop)<br />
Function<br />
In general, the unit is considered in operation if its supply fan is in operation.<br />
But, according to the set points, the fan may stop in the temperature control dead zone.<br />
Description<br />
To allow the operation of the unit it is necessary that set point 3111 is set to `On' and that the BM<strong>50</strong> logical input ID7 on<br />
the J5 connector is closed.<br />
The 3111 set point adjustment is available on the DC/DM<strong>50</strong> with the ON/OFF functionality.<br />
For each scheduled zone defined in Climatic<strong>50</strong>, it is possible to set the start/stop state. This functionality allows the<br />
unit to stop during a period of time in the day.<br />
When the Room temperature is within the regulation dead zone, for each scheduled zone defined in the Climatic<strong>50</strong> it is<br />
possible run or stop the fan<br />
3111 � Main On/Off.<br />
3351 � On/Off, adjustment by zone.<br />
3352 � On/Off in the temperature control dead zones, adjustment by zone.<br />
STAGGING START<br />
Function<br />
After a power shut-down, you may get the units to restart gradually in order to avoid overloading issues.<br />
Description<br />
The units do not need to be connected; they must simply have different pLan addresses, (see BM<strong>50</strong> pLan address<br />
configuration).<br />
This will enable them to restart (10 x their address number) seconds after the resumption of the power.<br />
Example:<br />
If a unit carries the address n°3, it will start again 30s (3 X 10 seconds) after the resumption of the power.<br />
HIGH EFFICIENCY FANS or/and WITH VARIABLE SPEED TRANSMISSION<br />
Function<br />
The supply fan variable speed option allows two functionalities;<br />
Progressive start or stop (used for the textile duct inflation)<br />
The speed reduction, in temperature control dead zone, in order to bring only the necessary fresh air quantity.<br />
Description<br />
The supply fan speed is originally fixed by the set point 3422.<br />
The speed entered in this set point corresponds to nominal air flow of the installation. This set point can only be adjusted<br />
on site.<br />
Progressive Start / Stop<br />
If set point 3423 is activated;<br />
During fan start up, for 30s, the speed is fixed by the threshold set point 3421. Then during the next 30s the fan<br />
accelerates gradually to reach the speed fixed in the set point 3422.<br />
During the fan stop, the speed gradually reduces to stop completely in 1 minute.<br />
CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 13