2132 � CO² rate measured value of the (ppm).<br />
3354 � CO² function authorization, adjustment by zone.<br />
3515 � CO² function mode [0-Min], [Min-Max].<br />
3513 � CO² rate (ppm), threshold until which the 0% or the minimum fresh air is maintained.<br />
3514 � CO² rate (ppm), threshold from which the minimum fresh air or the 100% is used.<br />
3512 � Maximum fresh air damper opening.<br />
Fresh air damper Calibration<br />
The real fresh air volume introduced into the system is not always proportional to the damper opening percentage. That<br />
is particularly true when the return air duct system is sized to give excessive pressure losses.<br />
It results with excessive fresh air input, and thus with an increase of the system exploitation costs. From now on, it is<br />
possible to calibrate the fresh air using three temperature probes: one in the blowing section, another in the return air<br />
and the last one in the outdoor temperature.<br />
Using these three probes, Climatic<strong>50</strong> calculates and memorizes the exact percentage of fresh air for each position of<br />
the damper.<br />
Blowing T° = Return T° x %Return Air + Fresh air T° x %Fresh Air<br />
This adjustment sequence takes place periodically when all heating and cooling elements are off.<br />
3516 � Fresh air damper calibration authorization.<br />
FREE COOLING<br />
From a room temperature need (Capacity Factor) the damper opens according to a proportional rule on the blowing<br />
temperature.<br />
0% need = Minimum fresh air.<br />
100% need = low limit threshold (3373) + 2K<br />
The user may choose to limit the fresh air damper operation with contacts or set points modification (see minimum fresh<br />
air § above). The outdoor temperature or humidity value may also limit the opening.<br />
Outdoor temperature<br />
The Free-Cooling is stopped if the outside temperature is higher than the return or room temperature.<br />
The Free-Cooling is stopped if the outside temperature is lower or higher than the threshold defined in set point (3511).<br />
Free cooling is forbidden on high limit for a set point adjustment over +20.0°c.<br />
Free cooling is forbidden on low limit for a set point adjustment lower than +20.0°c.<br />
Outdoor humidity (optional)<br />
If humidity control option is selected, the Free-cooling is stopped if the external absolute humidity (water weight) is<br />
higher than the indoor absolute humidity.<br />
Set point<br />
The Free-Cooling is stopped if the set point (3353) is No<br />
Free contact (optional)<br />
Stop of Free-Cooling by closing customized free contacts. (See minimum fresh air § above)<br />
[0% A.N.] = the register of air is completely closed.<br />
[100% A.N.] = the register of air is completely open.<br />
3353 � Economiser functionauthorization, adjustment by zone.<br />
3373 � Low limit blowing temperature threshold.<br />
3511 � Outdoor temperature threshold for authorization of the economiser function.<br />
3512 � Maximum fresh air damper opening<br />
CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 19