2132 � CO² rate measured value of the (ppm).<br />

3354 � CO² function authorization, adjustment by zone.<br />

3515 � CO² function mode [0-Min], [Min-Max].<br />

3513 � CO² rate (ppm), threshold until which the 0% or the minimum fresh air is maintained.<br />

3514 � CO² rate (ppm), threshold from which the minimum fresh air or the 100% is used.<br />

3512 � Maximum fresh air damper opening.<br />

Fresh air damper Calibration<br />

The real fresh air volume introduced into the system is not always proportional to the damper opening percentage. That<br />

is particularly true when the return air duct system is sized to give excessive pressure losses.<br />

It results with excessive fresh air input, and thus with an increase of the system exploitation costs. From now on, it is<br />

possible to calibrate the fresh air using three temperature probes: one in the blowing section, another in the return air<br />

and the last one in the outdoor temperature.<br />

Using these three probes, Climatic<strong>50</strong> calculates and memorizes the exact percentage of fresh air for each position of<br />

the damper.<br />

Blowing T° = Return T° x %Return Air + Fresh air T° x %Fresh Air<br />

This adjustment sequence takes place periodically when all heating and cooling elements are off.<br />

3516 � Fresh air damper calibration authorization.<br />

FREE COOLING<br />

From a room temperature need (Capacity Factor) the damper opens according to a proportional rule on the blowing<br />

temperature.<br />

0% need = Minimum fresh air.<br />

100% need = low limit threshold (3373) + 2K<br />

The user may choose to limit the fresh air damper operation with contacts or set points modification (see minimum fresh<br />

air § above). The outdoor temperature or humidity value may also limit the opening.<br />

Outdoor temperature<br />

The Free-Cooling is stopped if the outside temperature is higher than the return or room temperature.<br />

The Free-Cooling is stopped if the outside temperature is lower or higher than the threshold defined in set point (3511).<br />

Free cooling is forbidden on high limit for a set point adjustment over +20.0°c.<br />

Free cooling is forbidden on low limit for a set point adjustment lower than +20.0°c.<br />

Outdoor humidity (optional)<br />

If humidity control option is selected, the Free-cooling is stopped if the external absolute humidity (water weight) is<br />

higher than the indoor absolute humidity.<br />

Set point<br />

The Free-Cooling is stopped if the set point (3353) is No<br />

Free contact (optional)<br />

Stop of Free-Cooling by closing customized free contacts. (See minimum fresh air § above)<br />

[0% A.N.] = the register of air is completely closed.<br />

[100% A.N.] = the register of air is completely open.<br />

3353 � Economiser functionauthorization, adjustment by zone.<br />

3373 � Low limit blowing temperature threshold.<br />

3511 � Outdoor temperature threshold for authorization of the economiser function.<br />

3512 � Maximum fresh air damper opening<br />

CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 19