CUSTOMIZED INPUT/OUTPUT<br />
Function<br />
On the BM.<strong>50</strong> card and with the optional expansion board BE.<strong>50</strong>, it is possible to customize some input / output for<br />
remote control of the unit. So it is possible to customize<br />
• 5 digital outputs NC or NO set up with parameters 3841, 3842, 3843 and 3845<br />
• 6 digitals inputs set up by parameters 3851, 3852, 3853 and 3854<br />
• 4 analogical inputs (4-20mA or <strong>Lennox</strong> NTC temperature probe), set up with parameters 3861, 3862, 3863 et 3864<br />
Description<br />
Il est possible de paramétrer les fonctions suivantes :<br />
SORTIE DIGITALE NC ou NO - CONTACTS SECS<br />
Following information could be recovered from each contact :<br />
[Not Used.] No contact<br />
[Filter Al.] Filter fault<br />
[Blower Al.] Blowing fan fault<br />
[Comp. Al.] Compressor fault<br />
[Gas Al] Gaz fault<br />
[ElecH. Al] Electrical heater fault<br />
[Frost. Al] Alarm, freezing risk<br />
[Smoke. Al.] Smoke detector alarm<br />
[Heat. Mode] Heating mode<br />
[Humidif.] Humidifier pilote<br />
[Z:A] Unit operating Mode A<br />
[Z:B] Unit operating Mode B<br />
[Z:C] Unit operating Mode C<br />
[Uno] Unit operating Mode Inoccupied<br />
[Bms] Unit operating Mode BMS<br />
[LibrFree] Free for BMS acting<br />
[Exhaust 1] Drive exhaust fan n°1<br />
[Exhaust 2] Drive exhaust fan n°2<br />
[Exhaust 3] Drive exhaust fan n°3<br />
3841 � Setting of connector BM<strong>50</strong>-J17-N12.<br />
3842 � Setting of connector BE<strong>50</strong>-J5-N1.<br />
3843 � Setting of connector BE<strong>50</strong>-J6-N2.<br />
3844 � Setting of connector BE<strong>50</strong>-J7-N3.<br />
3845 � Setting of connector BE<strong>50</strong>-J8-N4.<br />
ENTREE DIGITALE 24V AC ou DC<br />
following orders can be sent on each contact:<br />
[Not Used] No contact<br />
[Sw Unoc.] Force Unoccupied Mode<br />
[Dis. Cp/AH] Stop of all compressors and auxillary heating<br />
[Dis. Comp. ] Stop of all compressors<br />
[Dis. <strong>50</strong>%Cp] Immediate stop of <strong>50</strong>% of the compressors<br />
[Dis. AuxH.] Stop of supplementary heating<br />
[Sw Dis.Cool] Cancellation of cooling mode<br />
[Sw Dis.Heat] Cancellation of heating mode<br />
[State Humi] Humidifier fault input<br />
[0% F.A. ] Force 0% fresh air<br />
[10% F.A.] Add 10% fresh air<br />
[20% F.A. ] Add 20% fresh air<br />
[30% F.A.] Add 30% fresh air<br />
[40% F.A.] Add 40% fresh air<br />
[<strong>50</strong>% F.A.] Add <strong>50</strong>% fresh air<br />
[100% F.A.] Force 100% fresh air<br />
[Low Speed] Force low speed ventilation<br />
[Free] Free for BMS system information.<br />
CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 25