Fault in Real Time Clock<br />

Description<br />

Error code: 070<br />

The real time clock card, incorporated in the Climatic card, is defective.<br />

Action<br />

� Fault signalling. Memorisation is displayed.<br />

Reset<br />

Automatic reset.<br />

Possible causes Solving the problem<br />

The battery is exhausted Replace the daughter card<br />

The daughter card is not inserted correctly Check the connection<br />

Extension card fault (BE<strong>50</strong>)<br />

Description<br />

Communication between the BM<strong>50</strong> and the BE<strong>50</strong> is down.<br />

Action<br />

� Compressors 3 and 4 stop, for the Flexy range.<br />

� Fault signalling. Memorisation is displayed.<br />

Reset<br />

Error code: 071<br />

The fault disappears automatically as soon as communication is reestablished.<br />

Possible causes Solving the problem<br />

Incorrect addressing of the BE<strong>50</strong> Configure the Serial Address dip-switches (on, off, off, off)<br />

BM<strong>50</strong> or BE<strong>50</strong> damaged Replace the defective component<br />

Problem with the BIOS Replace the BIOS with version 3A.57 or 3.64 or above<br />

Incorrect wiring or loose connection between<br />

BM<strong>50</strong> and BE<strong>50</strong><br />

Check connections and wiring<br />

CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 35