Gas Burner Faults<br />

Description<br />

Error code: 014, 015<br />

The gas burner control box has generated a fault and is no longer controlling the fume extractor fan.<br />

Action<br />

� The gas burner shuts down immediately.<br />

� Fault signalling.<br />

If a DS<strong>50</strong> is connected to the unit; Memorisation and diplay of all faults.<br />

Otherwise; Memorisation and display only of the 3rd daily fault.<br />

� Display of fault.<br />

014, 1st gas burner.<br />

015, 2nd gas burner<br />

Reset<br />

The burner restarts automatically 2 minutes after safety setting by electrically resetting the burner control box.<br />

The fault will no longer be reset automatically after 3 cutouts in the same day and must be reset <strong>manual</strong>ly.<br />

Note: The fault counter is cleared and reset every day at 11 am, provided the maximum number of faults has not<br />

been reached.<br />

Possible causes Solving the problem<br />

See IOM Flexy Read the documentation<br />

Problem with the wiring of the gas burners Check the connections<br />

CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 33