Gas Burner Faults<br />
Description<br />
Error code: 014, 015<br />
The gas burner control box has generated a fault and is no longer controlling the fume extractor fan.<br />
Action<br />
� The gas burner shuts down immediately.<br />
� Fault signalling.<br />
If a DS<strong>50</strong> is connected to the unit; Memorisation and diplay of all faults.<br />
Otherwise; Memorisation and display only of the 3rd daily fault.<br />
� Display of fault.<br />
014, 1st gas burner.<br />
015, 2nd gas burner<br />
Reset<br />
The burner restarts automatically 2 minutes after safety setting by electrically resetting the burner control box.<br />
The fault will no longer be reset automatically after 3 cutouts in the same day and must be reset <strong>manual</strong>ly.<br />
Note: The fault counter is cleared and reset every day at 11 am, provided the maximum number of faults has not<br />
been reached.<br />
Possible causes Solving the problem<br />
See IOM Flexy Read the documentation<br />
Problem with the wiring of the gas burners Check the connections<br />
CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 33