Display DC<strong>50</strong> or DM<strong>50</strong> is connected to the Climatic with the DT<strong>50</strong> screw connector.<br />

Connection must be carried out by the following cable:<br />

- Cable length up to 300m: AWG22 (0.34 mm ²), 2 pairs crossed with screen.<br />

- Cable length up to <strong>50</strong>0m: LiYCY-P (0.34 mm ²), 2 pairs with general shield.<br />

The cable length should not exceed <strong>50</strong>0m.<br />

For a better electromagnetic protection, <strong>Lennox</strong> recommends the use of LiYCY-P cable<br />

CONNECTION ON DT<strong>50</strong> REPARTITOR<br />

- +<br />

Terminal connection board installation guide DT <strong>50</strong><br />

The board is fitted with three "telephone" RJ12 plugs. Ensure the board is correctly connected.<br />

Standard connection is:<br />

BM<strong>50</strong> on connector C<br />

DC<strong>50</strong>/DM<strong>50</strong> on connector A or SC<br />

DS<strong>50</strong> on connector B<br />

DC<strong>50</strong> / DM<strong>50</strong><br />

3<br />

GND VL<br />

DT<strong>50</strong><br />

Jumpers:<br />

"Displays" are supplied directly by the Climatic board with 30Vdc. Take particular care at the path this 30V is taking when several<br />

boards are being used.<br />

J14 and J15 can switch on or off the direct current from the power supply:<br />

4<br />

2<br />

1<br />

1<br />

2<br />

3<br />

4<br />

CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 5