Compressors shut down on LP Cutoff<br />

Description<br />

Error code: 117, 127, 137, 147<br />

The low pressure switch of the circuit has been open for 2 minutes, while one compressor in the Circuit has operated<br />

for 2 minutes.<br />

The low pressure switch of the Circuit has been open for 1 hour.<br />

Action<br />

� Immediate shut down of the compressors in the circuit.<br />

� Fault signalling.<br />

If a DS<strong>50</strong> is connected to the unit; Memorisation and diplay of all faults.<br />

Otherwise; Memorisation and display only of the 3rd daily fault.<br />

� Display of fault.<br />

117, Circuit 1.<br />

127, Circuit 2.<br />

137, Circuit 3.<br />

147, Circuit 4.<br />

Reset<br />

Automatic reset of the fault as soon as the low pressure becomes greater than the safety pressure switch cutoff limit<br />

The fault will no longer be reset automatically after 3 cutouts in the same day and must be reset <strong>manual</strong>ly.<br />

Note: The fault counter is cleared and reset every day at 10 am provided the maximum number of faults has<br />

not been reached.<br />

Possible causes Solving the problem<br />

Not enough refrigerant in the circuit Adjust the refrigerant charge<br />

Faulty expansion valve Check that the expansion valve is operating correctly<br />

Filter drier blocked Replace the filter drier<br />

Faulty low pressure switch Replace the low pressure switch<br />

CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 41