COMMUNICATION<br />

MASTER/SLAVE<br />

Function<br />

Link several units in order to allow a “Master/Slave” relationship between each units.<br />

Description<br />

Configuration of the pLan network<br />

To configure the addresses of the cards for the pLan network, see chapter: (Configuring the pLan address of the BM<strong>50</strong>)<br />

For the pLan network, each unit must have a different address:<br />

Unit 1 � Master unit<br />

Units 2 to 12 � Slave units<br />

Master/Slave Modes<br />

Several master/slave modes are available and may be configured by using set points 3922 and 3923:<br />

Cold/hot Master/Slave mode:<br />

All the units are stand-alone, but:<br />

• If the master is calling for cooling, the heating adjustment of the slaves is inhibited.<br />

• If the master is calling for heating, the cooling adjustment of the slaves is inhibited.<br />

“Token” Mode:<br />

This mode limits the number of compressors in operation.<br />

Use set point 3922 to set the maximum number of compressors that can operate simultaneously for all the units<br />

connected.<br />

Back-up mode;<br />

The unit with the highest pLan address is used as a back-up in the event of a fault in another unit.<br />

In the event of different faults on several units, the following fault priority is applied:<br />

1. The unit stops<br />

2. Fault in one sensor or probe<br />

3. Fault in one or more compressors<br />

4. Fault in a back-up heater<br />

5. Temperature Limit fault<br />

6. Filter fault<br />

If the ambient temperature is exceeded, fault 013 or 023, the back-up unit will restart to compensate for the loss of power<br />

of the other units.<br />

Rotating back-up mode:<br />

Same as above, except the "back-up" unit changes every Tuesday at 09.00 if none of the other units is faulty.<br />

Master DC<strong>50</strong><br />

Function configurable using set point 3924:<br />

Activation of this function enables one, and only one, DC<strong>50</strong> to be connected for a maximum of 12 units.<br />

• The DC<strong>50</strong> must be connected to the Master unit (pLan address 1).<br />

• The functions between the Master BM<strong>50</strong> and its DC<strong>50</strong> are standard.<br />

• The Master BM<strong>50</strong> communicates its Start or Stop status to its slaves, the current range and the values<br />

of its temperature and minimum fresh air set points.<br />

• The slaves BM<strong>50</strong>s communicate a summary of their Alarms to the master. A 902 alarm on the master unit<br />

represents activation of a fault on slave unit 2 (903 for 3, etc).<br />

This function is incompatible with the Back-up mode.<br />

CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 43