COMMUNICATION<br />
MASTER/SLAVE<br />
Function<br />
Link several units in order to allow a “Master/Slave” relationship between each units.<br />
Description<br />
Configuration of the pLan network<br />
To configure the addresses of the cards for the pLan network, see chapter: (Configuring the pLan address of the BM<strong>50</strong>)<br />
For the pLan network, each unit must have a different address:<br />
Unit 1 � Master unit<br />
Units 2 to 12 � Slave units<br />
Master/Slave Modes<br />
Several master/slave modes are available and may be configured by using set points 3922 and 3923:<br />
Cold/hot Master/Slave mode:<br />
All the units are stand-alone, but:<br />
• If the master is calling for cooling, the heating adjustment of the slaves is inhibited.<br />
• If the master is calling for heating, the cooling adjustment of the slaves is inhibited.<br />
“Token” Mode:<br />
This mode limits the number of compressors in operation.<br />
Use set point 3922 to set the maximum number of compressors that can operate simultaneously for all the units<br />
connected.<br />
Back-up mode;<br />
The unit with the highest pLan address is used as a back-up in the event of a fault in another unit.<br />
In the event of different faults on several units, the following fault priority is applied:<br />
1. The unit stops<br />
2. Fault in one sensor or probe<br />
3. Fault in one or more compressors<br />
4. Fault in a back-up heater<br />
5. Temperature Limit fault<br />
6. Filter fault<br />
If the ambient temperature is exceeded, fault 013 or 023, the back-up unit will restart to compensate for the loss of power<br />
of the other units.<br />
Rotating back-up mode:<br />
Same as above, except the "back-up" unit changes every Tuesday at 09.00 if none of the other units is faulty.<br />
Master DC<strong>50</strong><br />
Function configurable using set point 3924:<br />
Activation of this function enables one, and only one, DC<strong>50</strong> to be connected for a maximum of 12 units.<br />
• The DC<strong>50</strong> must be connected to the Master unit (pLan address 1).<br />
• The functions between the Master BM<strong>50</strong> and its DC<strong>50</strong> are standard.<br />
• The Master BM<strong>50</strong> communicates its Start or Stop status to its slaves, the current range and the values<br />
of its temperature and minimum fresh air set points.<br />
• The slaves BM<strong>50</strong>s communicate a summary of their Alarms to the master. A 902 alarm on the master unit<br />
represents activation of a fault on slave unit 2 (903 for 3, etc).<br />
This function is incompatible with the Back-up mode.<br />
CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 43