SUPPLEMENT OF HEATING (Option)<br />

Fonction<br />

Units may be equipped with 3 types of supplementary heating:<br />

Gas (BG, FG et BD, FD)<br />

Hot water coils (BC, FC et BH, FH)<br />

Electric heaters (BC, FC et BH, FH)<br />

From a room temperature need (Capacity Factor) the supplement of heating stages are started and stopped with a predetermined<br />

order.<br />

Description<br />

Operation priority, Compressors / Additional heating<br />

From factory setting, in heat pump mode, Climatic starts compressors first and then if necessary, starts additional<br />

heating.<br />

This sequence may be reversed with set points for the ambient temperature regulation and for fresh air pre-heating.<br />

3324 � Priority inversion from compressors to supplementary heating, air temperature regulation, adjustment by zone.<br />

3332 � Priority inversion from compressors to supplementary heating, fresh air regulation, adjustment by zone.<br />

Operation authorization<br />

The user may choose to limit the operation of the compressors by using contacts or set points modification.<br />

Set points<br />

Stop of additional heating if the set point (3357) is set tp ‘No’.<br />

Note: The address (3357) can be set differently for zones A, B, C, Ino ou GTC<br />

Contact<br />

Stop of the gaz module if the free contacts [Dis. Cp/Ah] or [Dis. AuxH.] are closed. (See Customized Input / Output<br />

(BE.<strong>50</strong>)).<br />

3357 � Supplementary heating authorization adjustment by zone.<br />

ELECTRICAL HEATERS<br />

Electrical heaters are stopped if the outside temperature is above a threshold in set point (3721).<br />

The capacity of electrical heaters piloted by a Triac may be limited. The set point (3723) fixes the maximum threshold.<br />

For electrical heaters piloted by a Triac and positioned before the coil, if the mixing air temperature is below the threshold<br />

in set point (3722), the electrical heaters are activated to 100%.<br />

For electrical heaters piloted by a Triac and positioned after the coil, if the blowing air temperature is below the threshold<br />

in set point (3722), the electrical heaters are activated to 100%.<br />

Pour les résistances électrique pilotées par Triac et positionnées après la batterie de détente directe ; si la température<br />

de soufflage est inférieure au seuil de la consigne 3722 les résistances sont activées à 100%<br />

3721 � Outside air temperature threshold for electrical heaters authorization.<br />

3722 � Minimum temperature threshold, Triac.<br />

3723 � Maximum capacity threshold, Triac.<br />

HOT WATER<br />

Protection against freezing with minimum water flow.<br />

If the outside air temperature is below the set point (3331), the valve will open to a minimum fixed in the threshold (3332).<br />

Freezing fault<br />

In general, in case of detection of hot water coil icing, the valve will open to 100%. Due to certain hydraulic network,<br />

pumps or tracing, the coil protection is done by closing the valve. This can be activated with the set point 3733.<br />

3731 � Outside air temperature threshold for authorization, minimum water flow.<br />

3732 � Valve opening threshold , minimum water flow.<br />

3733 � Valve action in case of freezing fault.<br />

CLIMATIC<strong>50</strong> – IOM – Rooftops/ Aircoolair CL<strong>50</strong>-ROOFTOPS-IOM-1107-E 23