Technical Documentation Pressure Independent Characterized ...
Technical Documentation Pressure Independent Characterized ...
Technical Documentation Pressure Independent Characterized ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Selecting the Proper Flow Rate:<br />
The PICCV-20-010 (-PT) can be ordered in 6 GPM to 10 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 6 GPM flow rate.<br />
Solution: Order the PICCV-20-006<br />
Example 2: The application requires a 8.5 GPM flow rate.<br />
Solution: Order the PICCV-20-010 and re-program to the<br />
below setting for 8.5 GPM. As a standard, the<br />
PICCV is available in flows of 8 GPM and 9 GPM.<br />
If you desire 8.5 GPM and have a Normally Closed<br />
(NC) valve, simply reprogram the maximum setting<br />
to 82% and minimum setting of 0% as indicated on<br />
the chart below.<br />
Multi-Function<br />
Technology<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with MFT, Spring Return Actuator, P/T Ports (Optional)<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering,<br />
please specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 6 GPM flow rate is required, spring return actuator,<br />
2-10 VDC signal.<br />
Solution: PICCV-20-006 + LF24-MFT US + P-10019.<br />
Engineering Note: The 3/4” PICCV utilizes a uniquely engineered<br />
valve body to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered<br />
Multi-Function Technology®. The PICCV-20-010 offers nominal<br />
flow rates that are adjustable from 6 to 10 GPM. Please follow<br />
MFT guideline settings when configuring the PICCV MFT actuators<br />
in the field.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: LF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
3/4”, 6 – 10 GPM<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />
Default* Flow Adjustments**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-20-006(-PT) + LF24-MFT US 6 0.38 74% 0%<br />
6.5 0.41 75% 0%<br />
PICCV-20-007(-PT) + LF24-MFT US 7 0.44 77% 0%<br />
7.5 0.47 79% 0%<br />
PICCV-20-008(-PT) + LF24-MFT US 8 0.50 80% 0%<br />
8.5 0.54 82% 0%<br />
PICCV-20-009(-PT) + LF24-MFT US 9 0.57 83% 0%<br />
9.5 0.60 85% 0%<br />
PICCV-20-010(-PT) + LF24-MFT US 10 0.63 90% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />
Default* Flow Adjustments**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-20-006(-PT) + LF24-MFT US 6 0.38 100% 31%<br />
6.5 0.41 100% 28%<br />
PICCV-20-007(-PT) + LF24-MFT US 7 0.44 100% 27%<br />
7.5 0.47 100% 25%<br />
PICCV-20-008(-PT) + LF24-MFT US 8 0.50 100% 24%<br />
8.5 0.54 100% 22%<br />
PICCV-20-009(-PT) + LF24-MFT US 9 0.57 100% 19%<br />
9.5 0.60 100% 18%<br />
PICCV-20-010(-PT) + LF24-MFT US 10 0.63 100% 13%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />
21