Technical Documentation Pressure Independent Characterized ...
Technical Documentation Pressure Independent Characterized ...
Technical Documentation Pressure Independent Characterized ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
Dimensions<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with On/Off, Non-Spring Return Actuator<br />
LRCB24-3 LRCB24-3 with P/T Ports<br />
Line<br />
Volts<br />
WARNING<br />
Live Electrical Components!<br />
During installation, testing, servicing and troubleshooting of this product, it maybe<br />
necessary to work with live electrical components. Have a qualified licensed electrician<br />
or other individual who has been properly trained in handling live electrical components<br />
perform these tasks. Failure to follow all electrical safety precautions when exposed<br />
to live electrical components could result in death or serious injury.<br />
1<br />
2.6"<br />
[66]<br />
E F<br />
Wiring Diagram<br />
24 VAC Transformer<br />
a open<br />
a closed<br />
3.22"<br />
[82]<br />
The indication of direction<br />
is valid for switch position 1.<br />
D<br />
1.69"<br />
[42]<br />
a<br />
6.5" [165]<br />
B<br />
A<br />
3<br />
0.78" [20]<br />
Blk (1) Common –<br />
Red (2) +<br />
Wht (3) +<br />
1 0<br />
C<br />
2.34"<br />
[59.4]<br />
FlowSetR Dimensions<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 4.80 [122] 4.6 [117] 4.02 [102] 2.28 [58] 1.04 [24.4] 1.3 [33]<br />
3/4" NPT 5.25 [133] 5.03 [128] 4.22[107] 2.38 [61] 1.04 [24.4] 1.3 [33]<br />
1" NPT 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [40.6] 1.60 [40.6]<br />
3<br />
®<br />
LRCX24-3<br />
Notes:<br />
1 Provide overload protection and disconnect as required.<br />
Actuators may also be powered by 24 VDC.<br />
Meets cULus requirements without the<br />
need of an electrical ground connection.<br />
LRCB24-3 On/Off<br />
D146<br />
W569<br />
2.6"<br />
[66]<br />
E F<br />
3.22"<br />
[82]<br />
D<br />
1.69"<br />
[42]<br />
6.5" [165]<br />
B<br />
A<br />
C<br />
2.34"<br />
[59.4]<br />
0.78" [20] FlowSetR Dimensions<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 5.3 [135] 4.6 [117] 5.4 [137] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />
3/4" NPT 5.8 [147] 5.03 [128] 5.7 [145] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />
1" NPT 7.05 [179] 6.85 [174] 6.05 [154] 4.0 [102] 1.60 [40.6] 2.90 [73.65]<br />
D147<br />
69