Technical Documentation Pressure Independent Characterized ...
Technical Documentation Pressure Independent Characterized ...
Technical Documentation Pressure Independent Characterized ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
2.16 CONTROL VALVES<br />
®<br />
A. Control Valves: Factory fabricated of type, body<br />
material, and pressure class based on maximum<br />
pressure and temperature rating of the piping<br />
system, unless otherwise indicated.<br />
B. <strong>Pressure</strong> <strong>Independent</strong> Control Valves<br />
a. Manufacturers:<br />
i. BELIMO AIRCONTROLS (USA), INC.<br />
b. The modulating control valves shall be<br />
pressure independent.<br />
c. The control valves shall accurately control the flow<br />
from 0 to 100% full rated flow with an equal<br />
percentage flow characteristic. The flow shall not<br />
vary more than +/- 5% due to system pressure<br />
fluctuations across the valve with a minimum of<br />
5 PSID across the valve.<br />
d. Forged brass body rated at no less than 400 PSI,<br />
chrome plated brass ball and stem, female NPT<br />
union ends, dual EPDM lubricated O-rings and<br />
TEFZEL characterizing disc.<br />
e. Combination of actuator and valve shall provide a<br />
minimum close-off pressure rating of 200 PSID.<br />
f. The control valve shall require no maintenance<br />
and shall not include replaceable cartridges.<br />
g. All actuators shall be electronically programmed<br />
by use of a handheld programming device or<br />
external computer software. Programming using<br />
actuator mounted switches or multi-turn actuators<br />
are NOT acceptable. [Actuators for 3-wire<br />
floating (tri-state) on 1/2” – 1” pressure<br />
independent control valves shall fail in place<br />
and have a mechanical device inserted<br />
between the valve and the actuator for the<br />
adjustment of flow.] [Actuators for two-position<br />
1/2” – 1” pressure independent control<br />
valves shall fail in place and have a mechanical<br />
device inserted between the valve and the<br />
actuator for the adjustment of flow.] [Actuators<br />
shall be provided with an auxiliary switch to<br />
prove valve position.]<br />
h. The actuator shall be of the same manufacturer<br />
as the valve, integrally mounted to the valve at the<br />
factory via a single screw on a four-way DIN<br />
mounting-base.<br />
i. The control valve shall require no maintenance<br />
and shall not include replaceable cartridges.<br />
j. The manufacturer shall warrant all components<br />
for a period 5 years from the date of production,<br />
with the first two years unconditional.<br />
k. The use of pressure independent valves piped in<br />
parallel to achieve the rated coil flow shall be<br />
permitted. Actuators shall be electronically<br />
programmed to permit sequencing the flow with a<br />
single control output point. The use of external<br />
devices to permit sequencing is NOT acceptable.<br />
Specifying <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong><br />
Control Valves (1/2” – 2”)<br />
Specifying <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves Master Format<br />
To be inserted into Section 15900 – HVAC Instrumentation and Controls<br />
To be inserted into Section 15181 – HYDRONIC PIPING<br />
2.6 CONTROL VALVES<br />
K. Calibrated Balancing Valves and Automatic<br />
Flow-Control Valves shall not be required on devices<br />
where pressure independent control valves are<br />
installed.<br />
NOTE TO BE ADDED TO THE PIPING DETAIL:<br />
Strainers shall not be required in front of each pressure<br />
independent control valve. A Type 20 strainer (or<br />
equivalent) should be installed in the system, in<br />
additional to other system strainers.<br />
To be inserted into Section 15950 – TESTING,<br />
ADJUSTING, AND BALANCING<br />
3.11 PROCEDURE FOR HYDRONIC SYSTEMS<br />
[CHOOSE ONE OF THE FOLLOWING TWO PARAGRAPHS]<br />
H. Systems installed with pressure independent control<br />
valves shall not require hydronic system balancing.<br />
H. Systems installed with pressure independent valves<br />
shall require verification of flow for [10%] [20%]<br />
[25%] of the total<br />
installed product. Exact locations of tested product<br />
to be coordinated with the design engineer.<br />
75