J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

The Best Way to Control Flow<br />

Maintain design flow independent of<br />

pressure variations<br />

The PICCV is a two-way valve that will<br />

supply a specific flow for each degree<br />

of ball opening regardless of pressure<br />

variations in a system.<br />

Flow accuracy ≤ ± 5% (5 to 50 PSI)<br />

(absolute)<br />

Variation due to ≤ ± 5% (5 to 50 PSI)<br />

manufacturing<br />

tolerances<br />

Hysteresis ≤ 1%<br />

(absolute)<br />

Operation<br />

PICCV consists of a differential pressure<br />

regulator in series with a control valve.<br />

The amount of flow that passes through the<br />

valve is controlled by the use of a pressure<br />

regulator that moves according to the<br />

change in pressure above and below it.<br />

All pressure changes are absorbed by<br />

the pressure regulator allowing the<br />

differential pressure to be held constant<br />

over the control valve section thereby<br />

giving the same flow.<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve TM (PICCV)<br />

Flow Rate (GPM)<br />

14<br />

12<br />

10<br />

8<br />

6<br />

4<br />

2<br />

0<br />

Water<br />

enters<br />

valve –<br />

pressure<br />

is P1 (high)<br />

Water passes<br />

through regulator,<br />

disc, and ball –<br />

pressure drops<br />

PICCV Performance<br />

Operating Differential Range of 5 – 50 PSI<br />

0 5 10 15 20 25 30 35 40 45 50<br />

Differential <strong>Pressure</strong> PSI<br />

Regulator<br />

Section<br />

Control Valve<br />

Section<br />

Low pressure pulls regulator<br />

down against the spring force<br />

hence reducing the regulator<br />

opening, reducing the flow.<br />

100%<br />

90%<br />

80%<br />

70%<br />

60%<br />

50%<br />

40%<br />

Water exits<br />

valve –<br />

pressure<br />

is P2 (low)<br />

Ports sense pressure drop<br />

and transfer it through this<br />

channel below regulator<br />

% Ball Opening<br />