when (H T ) < (V T )<br />

Simple venting configurations<br />

REQUIRED<br />

VERTICAL RISE<br />

IN FEET<br />

V T<br />

FIGURE 15<br />

See graph to determine the required vertical rise V T for the<br />

required horizontal run H T .<br />

HORIZONTAL VENT RUN PLUS OFFSET IN FEET H HT<br />

The shaded area within the lines represents acceptable<br />

values for H and V .<br />

T T<br />

For vent configurations requiring more than zero 90° elbow<br />

(top exit) or one 90° elbow (rear exit), the following formulas<br />

apply:<br />

Formula 1: H T < V T<br />

Formula 2: H T + V T < 40 feet<br />

VERTICAL TERMINATION<br />

B<strong>CDV34</strong> / <strong>CDV34</strong> BCDV33 / CDV33<br />

Example 6:<br />

V1 V2 VT H 1<br />

H 2<br />

HR HO FIGURE 16<br />

H 1<br />

90°<br />

=5 ft<br />

=10 ft<br />

= V + V = 5 + 10 = 15 ft<br />

1 2<br />

=3 ft<br />

= 2.5 ft<br />

= H + H = 3 + 2.5 = 5.5 ft<br />

1 2<br />

= .03(three 90° elbows - 90°)<br />

= .03(90 + 90 + 90 - 90) = 5.4 ft<br />

H =H + H = 5.5 + 5.4 = 10.9 ft<br />

T<br />

R O<br />

H + V = 10.9 + 15 = 25.9 ft<br />

T T<br />

V 1<br />

H 2<br />

90°<br />

V 2<br />

90°<br />

Formula 1: H < V T T<br />

10.9 < 15<br />

Formula 2: H + V < 40 feet<br />

T T<br />

25.9 < 40<br />

Since both formulas are met, this vent configuration is acceptable.<br />

W415-0345 / L / 03.05.09<br />

13