CDV34 Gas Fireplace - Continental Fireplaces
CDV34 Gas Fireplace - Continental Fireplaces
CDV34 Gas Fireplace - Continental Fireplaces
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
24<br />
MINIMUM MANTLE<br />
AND ENCLOSURE<br />
CLEARANCES<br />
Mantle clearance can vary according to the mantle depth.<br />
Use the graph to help evaluate the clearance needed.<br />
Combustible materials must be installed flush with the<br />
front of the fireplace but must not cover any of the black<br />
face-area of the fireplace. Non-combustible material (brick,<br />
stone or ceramic tile) may protrude past the face of the<br />
fireplace.<br />
FIGURES 46a&b<br />
35 5/8"<br />
6"<br />
W415-0345 / L / 03.05.09<br />
8" MANTLE<br />
6"<br />
4"<br />
8"<br />
TOP OF<br />
FIREPLACE<br />
6"<br />
4"<br />
2"<br />
2"<br />
2"<br />
CDV33<br />
2"<br />
1"<br />
FIGURE 47<br />
VENT SLEEVE<br />
35 5/8"<br />
63"<br />
49"<br />
34"<br />
20"<br />
6"<br />
6"<br />
1"<br />
6"<br />
1"<br />
2"<br />
2"<br />
2"<br />
BCDV33<br />
2"<br />
1"<br />
<strong>CDV34</strong><br />
2"<br />
1"<br />
STEEL<br />
HEADER<br />
B<strong>CDV34</strong><br />
2"<br />
1"<br />
FIGURE 48<br />
VENT SLEEVE<br />
NON-COMBUSTIBLE<br />
MATERIAL<br />
FIGURE 49<br />
FIGURE 50