14<br />
when (H ) > (V )<br />
T T<br />
Simple venting configurations<br />
See graph to determine the required vertical rise V T for the<br />
required horizontal run H T .<br />
MAXIMUM<br />
VERTICAL<br />
RISE IN<br />
FEET<br />
V T<br />
HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable<br />
values for H and V .<br />
T T<br />
For vent configurations requiring more than two 90° elbow<br />
(top exit) or one 90° elbow (rear exit), the following formulas<br />
apply:<br />
Formula 1: H < 3V T T<br />
Formula 2: H + V < 40 feet<br />
T T<br />
Example 7:<br />
W415-0345 / L / 03.05.09<br />
B<strong>CDV34</strong> / <strong>CDV34</strong><br />
90°<br />
V 1<br />
H 1<br />
VERTICAL TERMINATION<br />
FIGURE 17<br />
BCDV33 / CDV33<br />
90°<br />
V 2<br />
FIGURE 18<br />
90°<br />
H 2<br />
V 3<br />
90°<br />
V1 V2 V3 VT H 1<br />
H 2<br />
HR HO =2 ft<br />
=1 ft<br />
=1.5 ft<br />
= V + V + V = 2 + 1 + 1.5 = 4.5 ft<br />
1 2 3<br />
=6 ft<br />
=2 ft<br />
= H + H = 6 + 2 = 8 ft<br />
1 2<br />
= .03(four 90° elbows - 90°)<br />
= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft<br />
H =H + H = 8 + 8.1 = 16.1 ft<br />
T<br />
R O<br />
H + V = 16.1 + 4.5 = 20.6 ft<br />
T T<br />
Formula 1: H < 3V T T<br />
3V = 3 x 4.5 = 13.5 ft<br />
T<br />
16.1 > 13.5<br />
Since this formula is not met, this vent configuration is unacceptable.<br />
Formula 2: H + V < 40 feet<br />
T T<br />
20.6 < 40<br />
Since only formula 2 is met, this vent configuration is unacceptable<br />
and a new fireplace location or vent configuration<br />
will need to be established to satisfy both formulas.<br />
Example 8:<br />
V1 V2 VT H 1<br />
H 2<br />
H 3<br />
HR HO H 1<br />
90°<br />
V 1<br />
H 2<br />
90°<br />
45°<br />
H 3<br />
FIGURE 19<br />
V 2<br />
=1.5 ft<br />
=5 ft<br />
= V + V = 1.5 + 5 = 6.5 ft<br />
1 2<br />
=1 ft<br />
=1 ft<br />
=10.75 ft<br />
= H + H + H = 1 + 1 + 10.75 = 12.75 ft<br />
1 2 3<br />
= .03(three 90° elbows + one 45° elbow - 90°)<br />
= .03(90 + 90 + 90 + 45 - 90) = 6.75 ft<br />
H =H + H = 12.75 + 6.75 = 19.5 ft<br />
T<br />
R O<br />
H + V = 19.5 + 6.5 = 26 ft<br />
T T<br />
90°<br />
Formula 1: H < 3V T T<br />
3V = 3 x 6.5 = 19.5 ft<br />
T<br />
19.5 = 19.5<br />
Formula 2: H + V < 40 feet<br />
T T<br />
26 < 40<br />
Since both formulas are met, this vent configuration is acceptable.