23.10.2013 Views

Design and Specification Guidelines - Gaston County Schools

Design and Specification Guidelines - Gaston County Schools

Design and Specification Guidelines - Gaston County Schools

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Design</strong> <strong>and</strong> <strong>Specification</strong> <strong>Guidelines</strong> <strong>Gaston</strong> <strong>County</strong> <strong>Schools</strong><br />

Updated: March 6, 2012 <strong>Gaston</strong>ia, NC 28054<br />

J. <strong>Design</strong> St<strong>and</strong>ards<br />

1. Verify existing conditions for Pressure Reducing Valve (PRV) installation<br />

requirements<br />

2. Upgrade existing utility service (electric, water, gas (excluding kitchen); do not<br />

add meters; single site service preferred, if economically feasible.<br />

3. One (1) key operated Hose Bib, under lavatory in toilet rooms containing a floor<br />

drain<br />

4. Floor drain in student one-holers<br />

5. No trap primers<br />

6. One Cut Off (hallway ceiling) per group bath<br />

7. One Freeze Proof, Key Operated, recessed, outside hose bib per long building<br />

side (window cleaning, pressure washing) approximately every 100 feet at 18”<br />

above grade<br />

8. For major outdoor equipment yards, provide freeze-proof hose bibs<br />

9. No internal roof drains<br />

10. Lavatory in classrooms for<br />

a) Pre-k to 5 th Grade (Elementary)<br />

b) Elkay H<strong>and</strong> Wash-up Sink, Type 304; model CH51716C (w/ gooseneck<br />

spout faucet)<br />

11. Hot Water to<br />

a) Staff toilets<br />

b) Teachers workroom<br />

c) Custodial closet<br />

d) Place tank on mechanical room floor<br />

e) All Pre-K h<strong>and</strong> sinks at 80 degrees F to 109 degrees F<br />

f) Nearest toilets to Cafeteria<br />

g) Teacher science table<br />

h) Science prep rooms<br />

12. Cast iron fixtures only (no china lavatory fixtures)<br />

13. Ice maker water connector box to Resource/Teacher workrooms<br />

14. Sewer Piping<br />

a) Single-story buildings: PVC piping<br />

b) Multi-story buildings: Cast iron piping<br />

15. No PVC valves<br />

16. Exterior grease traps for Kitchen<br />

a) Must be accessible by pump truck<br />

b) Precast concrete construction<br />

17. No off-set flanges<br />

18. No wall mounted toilets<br />

19. Manhole required where any new sanitary sewer plumbing ties into existing<br />

sewer (if feasible)<br />

20. Trace wire required for any non-conducting underground piping<br />

*=Preferred Br<strong>and</strong>; Bid Alternate Required Page 20 of 38 Pages