3. Installation and Noise Elimination<br />

Pay due attention to the installation environment of the con<strong>tr</strong>oller.<br />

3.1 Installation Environment<br />

(1) When installing and wiring the con<strong>tr</strong>oller, do not block the cooling ventilation holes. (Insufficient<br />

ventilation will not only prevent the con<strong>tr</strong>oller from demons<strong>tr</strong>ating its full performance, but it may also<br />

cause breakdown.)<br />

(2) Prevent foreign matter from entering the con<strong>tr</strong>oller through the ventilation holes. Since the enclosure<br />

of the con<strong>tr</strong>oller is not dustproof or waterproof (oilproof), avoid using the con<strong>tr</strong>oller in a place subject<br />

to significant dust, oil mist or splashes of cutting fluid.<br />

(3) Do not expose the con<strong>tr</strong>oller to direct sunlight or radiating heat from a large heat source such as a<br />

heat <strong>tr</strong>eatment furnace.<br />

(4) Use the con<strong>tr</strong>oller in an environment free from corrosive or inflammable gases, under a temperature<br />

of 0 to 40°C and humidity of 85% or less (non-condensing).<br />

(5) Use the con<strong>tr</strong>oller in an environment where it will not receive any external vibration or shock.<br />

(6) Prevent elec<strong>tr</strong>ical noise from entering the con<strong>tr</strong>oller or its cables.<br />

3.2 Power Supply<br />

The power supply specification is 24 VDC ± 10%.<br />

(Supply current: 2 A max.)<br />

3.3 Noise Elimination and Grounding<br />

This section explains how to eliminate noise in the use of the con<strong>tr</strong>oller.<br />

(1) Wiring and power supply<br />

[1] Provide a dedicated class D grounding using a wire with a size of 2.0 to 5.5 mm 2 or larger.<br />

<s<strong>tr</strong>ong>Con<strong>tr</strong>oller</s<strong>tr</strong>ong><br />

Other<br />

equipment<br />

<s<strong>tr</strong>ong>Con<strong>tr</strong>oller</s<strong>tr</strong>ong><br />

Other<br />

equipment<br />

Use a cable of a<br />

maximum possible<br />

size and keep the<br />

wiring length at a<br />

minimum.<br />

Metal frame<br />

Class D grounding Good Avoid this grounding method.<br />