Master Control Facility – Hassan<br />
Phase sequence<br />
indicator<br />
DG auxiliary<br />
system<br />
Emergency Power<br />
OFF (EPO)<br />
Modes of<br />
operation<br />
Neutral contactor<br />
: PSI shall be provided with spring return type ON / OFF selector switch.<br />
: All DG auxiliary motor control circuits are to be placed under respective<br />
DG incoming air circuit breaker compartments.<br />
: EPO switch shall shut down the unit by activating the shunt trip of the<br />
ACBs in local & remote operation.<br />
: Manual operation<br />
: Solo operation and<br />
: Automatic operation<br />
: Solo mode operation<br />
− DG neutral Contactor to close automatically before closing of respective<br />
DG breaker.<br />
− Neutral Contactor to trip after tripping of respective DG’s.<br />
− Selector switch for enabling / disabling the neutral contactor shall be<br />
provided.<br />
: Parallel operation<br />
-Only master DG neutral contactor should be ON.<br />
-Master DG neutral tripping shall trip all DG circuit breakers.<br />
Semi Modular substation LT panel –Specification 8