7.1 Features:<br />
a. Auto trip on earth fault & fuse failure<br />
b. Mechanical tripped on fault indication.<br />
c. Anti-reflex operating handle.<br />
d. LV Pilot cable box and protection compartment. MV cable box to comply in<br />
accordance with EATS 41-26. Modular construction with removable side sheets<br />
on three sides for better access required during installation & maintenance.<br />
Should have fully interlocked cable test access cover.<br />
e. Cast resin encapsulated bus bars in air. Bus chamber to be of extensible version.<br />
f. Flange bolts accordance with EATS 35-1, (or can be fitted with outgoing cable<br />
box).<br />
g. IP55 outdoor enclosure or better version.<br />
7.2 Switchgears operation : Switchgears are to be mounted in such a way its handle<br />
operation shall confirm to per IS 4237<br />
-ON Closing –Clockwise i.e., Vertically upward<br />
-OFF Opening –Anti-clockwise i.e., Vertically down ward<br />
8.0 Vacuum Circuit Breaker: IP 54 Enclosure<br />
a. The unit shall consist of 11KV, 630Amps VCB (for Controlling transformer),<br />
load breaking and fault breaking type fitted with three 630 Amps continuously<br />
rated Vacuum insulated bus bars and arrangement for cable to the primary side<br />
of the transformer.<br />
b. The circuit breaker shall be suitable for manual closing and opening and also for<br />
provision for remote tripping in future.<br />
c. The operating mechanism shall be direct hand operated trip free with a<br />
mechanically operated indicator, positively coupled to the operating mechanism<br />
to indicate whether the breaker is in the closed or in the open position.<br />
d. Voltage Indication: There should be arrangement to check whether the cable<br />
connecting tot the isolator is live or not.<br />
e. The indications for ON/OFF/EARTH of the Isolator & Breaker Switches should<br />
be visible from outside even with the enclosure.<br />
f. Current Transformer: The Ratio of the CTs shall be suitable for Controlling<br />
transformer as specified. The VA burden of the CTs shall be sufficient to<br />
supply the energy required by the relay for normal operation and tripping of the<br />
circuit breaker.<br />
g. Protection System: The protection system should be provided. It must provide<br />
immediate protection and can detect faults instructing the circuit breaker to trip<br />
in less than 40ms.It must have improved operation and Control with the Relay<br />
settings clearly displayed on the front of the panel.<br />
It shall have the provision for the trip test on circuit breaker. The trip inhibit<br />
facility allows the Relay to be tested without tripping the circuit breaker.<br />
Secondary injection can also be carried out using conventional test equipments.<br />
The switchgear and switchboards shall be designed so that the position of the<br />
different devices is visible to the operator on the front of the switchboard and<br />
operations are visible as well.<br />