voltage and frequency are subject to variation as per statutory limits governed by<br />

Indian Electricity Rules 1956 with latest amendments in force.<br />

DESIGN CRITERIA<br />

4.1 The 11kV Switchgear shall be installed at the location shown in the SLD. The 11kV<br />

distribution system, Vacuum Circuit Breaker shall be used to Control and isolate the<br />

11kV / 433V Cast Resin dry type distribution transformers / HT Consumers<br />

connected through 11kV grade underground cable at distribution center.<br />

4.2 The Switchgear and component thereof shall be capable of withstanding the<br />

mechanical and thermal stresses of short circuit listed in ratings and requirements<br />

clause without any damage or deterioration of the materials.<br />

4.3 For continuous operation at specified ratings temperature rise of the various<br />

Switchgear components shall be limited to permissible values stipulated in the<br />

relevant standard and / or this specification.<br />

4.4 The equipment offered shall be suitable for continuous satisfactory operation as per<br />

site condition specified elsewhere.<br />

5.0 Fabrication:<br />

Totally modular design concept.<br />

Free standing, floor mounting and suitable for out-door installation.<br />

The panel shall have easily removable and interchangeable sections.<br />

Required service clearances shall be provided to carry out preventive and remedial<br />

maintenance from front and rear side.<br />

The panel shall be naturally convection-cooled & shall allow continuous full-load<br />

operation, maintaining the temperatures within tolerance level of components.<br />

Each bus bar compartment should have a barrier with 1.6 mm thick electro galvanized<br />

coated / painted with fire resistance paint.<br />

The degree of protection for the panel shall be IP 54 for VCB & IP 55 for LBS<br />

6.0 GENERAL FINISH<br />

The equipment should be totally enclosed, metal clad, vermin and dust proof suitable<br />

for tropical climate use as detailed above. The body of the cubicle should be of<br />

metalised and rust free.<br />

6.1 Type of equipment<br />

The equipment shall be compact, totally enclosed in as self contained self contained<br />

self supporting compartment, mounted on base frame or channels. The assembly<br />

shall be equipped with common power bus bar, load break Switches and Vacuum<br />

circuit breaker as specified in specific requirement as above. All medium voltage<br />

parts should be totally enclosed.<br />

6.2 Bus bars:<br />

a. Busbar material – Copper<br />

b. The bus bars shall be Epoxy insulated High-purity electrolyte grade copper E-Cu 57<br />

confirming to latest IS standard of 120 % rating of the switchgears.<br />

Ele. Conductivity : 100% as per IAC Standard<br />

Confirming to: DIN 1759, DIN 40 500 and relevant bus bar IS standard<br />

Page 12 of 23