Master Control Facility – Hassan<br />

3<br />

Microcontroller based UV & OV Relays (For T1 & T2)<br />

Voltage Vn -110/240/415V settable at site, 50 Hz +/- 2.5 Hz, Auxiliary power<br />

supply: 24-110V AC/DC, Settings -Fault Voltage Vs -OV mode: 105-180% of<br />

Vn in steps of 5%, UV mode: 95-20% of Vn in steps of 5%, High Set Vhs -OV<br />

mode 110-180% of Vn in steps of 10%, -UV mode: 90-20% of Vn in steps of<br />

10%, Trip Time Characteristics -Normal Inverse NI -3.5 Sec in OV mode &<br />

5.7 in UV mode, Defnite Time -01, 10 and 100 Secs, Accuracy -+/- 5% of Vn,<br />

Auxiliary Contacts - 2 Pairs of self reset C/O contacts, Mounting -Panel<br />

mounting (Flush) type, Relay operation should not be affected by stray<br />

magnetic field. Make: L&T Model MV12A or equivalent in Siemens / Areva<br />

T&D / ASEA Brown Boveri<br />

4<br />

4<br />

Protection Relay (For T1 & T2)<br />

3Ph OC+EF+highset, Communication and breaker control with RS 485, Micro<br />

Controller based, LS OC (20-200% step 5%) HS O/C (0.2-40) in step of 0.2 In<br />

or disable & LS EF (5-80% step 5%), HS EF (0.1 to 20) on step of 0.1 On or<br />

disable, HS delay (0.1 to 2 Sec) step 0.01 sec or instantaneous, Draw out<br />

type, Auto doubling of HS, relay co-ordination, self testing & display of<br />

parameters, Site selectable trip time characteristics (NI, VI, EI & Definite<br />

Time), TMS 0.1-1.6 step 0.05, Auxiliary contacts 2NO+2NC, Auxiliary supply:<br />

24-110V AC/DC, CT Rating: 5A. Make: L&T Model MC61C or equivalent in<br />

Siemens / Areva T&D / ASEA Brown Boveri<br />

2<br />

5<br />

Digital Meter (For T1, T2, G1, G2 & G3)<br />

True RMS measuring meter to read L-L/L-N voltage, Current per phase /<br />

neutral current, Frequency, Phase rotation / Vmax. and current demand per<br />

phase, Vmin. per phase, %age of load circular bar graph. Capable of<br />

measuring power parameters viz., kW & kWh, kVA & kVAh, kVAr & kVARh,<br />

import & export etc., The meter shall be capable of reading the voltage as<br />

well as current (THD) Harmonic, Three phase at once, bright LED display.<br />

Communication port –RS 485 and Industrial standard communication<br />

protocol – MODBUS, Auxiliary power supply: 24 VDC. Make: Satec<br />

PM130EH<br />

5<br />

6<br />

7<br />

Differential Protection Relay (For G1, G2 & G3)<br />

Device code: 87, 50/51, 50LBB, 64S / 87N, Design: Numeric, Functions:<br />

Generator differential, bias % with dual adjustable slope, OC, stator EF & CB<br />

failure protection, Features: 1A or 5A site selectable, display of parameters,<br />

waveform capture feature, built in supervision & RS485 port, 4 C/O, S/R or<br />

H/R or time delay 1 C/O for self supervision, Flush mounting draw out type,<br />

Auxiliary supply 24-110V AC/DC. Make: L&T Model MD32G or equivalent in<br />

Siemens / Areva T&D / ASEA Brown Boveri<br />

Switch Disconnector Fuse Units (SDFU)<br />

Triple Pole with isolable Neutral (TPN), 415V, 50 Hz, Panel mounting type<br />

interrior version with operating mechanism and handle without HRC fuse<br />

links. Confirming to IS 13947 (Part 3), Accessories: Terminal shrouds, Fuse<br />

shrouds, Fuse barriers<br />

Make: L&T F-Line FNX series / Schneider MG Fupact SDF / Siemens -<br />

Sentron Superswitch<br />

3<br />

7a Rating: 630 Amps 15<br />

Semi Modular substation LT panel –Specification 10