Impulse withstand voltage - 75 kV<br />
Busbar rating - 120 % of rated continuos current<br />
Application - 1MVA Transformer switching<br />
Integral Earth switch – required<br />
Type: Horizontal draw out type with cradle assembly & metal<br />
ramp<br />
Operation -<br />
Spring closing mechanism - Electrical motor operated OR<br />
Solenoid<br />
Breaker Closing - Manual & Electrical through TNC switch /<br />
closing coil (110 V a.c derived from P.T)<br />
Under voltage release - 110 V a.c derived from P.T<br />
Shunt trip coil - 24 V d.c<br />
Safety interlock 7 locking facility – Required<br />
……………………………………………………………………<br />
2.1 Metering: Digital TVM for measuring power parameters,<br />
energy, harmonic parameters etc.,. with SNMP / RS 485 output<br />
interface. Software for remote M&C shall be supplied.<br />
Make: Satec. Model : PM 130 EH<br />
Analog Voltmeter, Size: 96 x 96 with selector switch<br />
Max. demand type Analog Ammeter ; Size: 96 x 96 with selector<br />
switch<br />
Phase sequence meter Size: 96 x 96 with selector switch<br />
……………………………………………………………………<br />
2.2 Protection Relay: Microprocessor based transformer<br />
protection relay with SNMP / RS 485 output interface.<br />
Features: 3 PHASE OVER CURRENT, EARTH FAULT RELAY +<br />
THERMAL FOR TRANSFORMER, 20-110V AC/DC<br />
Device code: 50/51, 46, 49<br />
Design: Numeric<br />
Functions: Low set and High set Over current<br />
Low set and High set Earth Fault with site selectable Trip<br />
characteristics, Definite inverse time tripping Thermal overload.<br />
Display of parameters, built in self supervision, RS 485 Port<br />
communication<br />
Make: L&T, Model: IM 30 T<br />
Software for remote M&C shall be supplied.<br />
……………………………………………………………………<br />
2.3 Master trip relay: High speed Relay with manual reset<br />
Type VAJH 13, Alstom make<br />
………………………………………………………………….<br />
2.4 Metering & protection CT's - Resin cast dry type<br />
Single phase, 2 core<br />
Ratio – 75-150/ 5 - 5 A<br />
Core - 1: Class - 1.0 15 VA<br />
Core II - Class 5P10, 15 VA<br />
Suitable for STC of 26.3 kA for 1 sec<br />
…………………………………………………………………….<br />
VCB BOM<br />
mentioned<br />
Sl 2.0 to<br />
2.11 is for<br />
individual<br />
VCB<br />
modules<br />
Page 6 of 23