Impulse withstand voltage - 75 kV<br />

Busbar rating - 120 % of rated continuos current<br />

Application - 1MVA Transformer switching<br />

Integral Earth switch – required<br />

Type: Horizontal draw out type with cradle assembly & metal<br />

ramp<br />

Operation -<br />

Spring closing mechanism - Electrical motor operated OR<br />

Solenoid<br />

Breaker Closing - Manual & Electrical through TNC switch /<br />

closing coil (110 V a.c derived from P.T)<br />

Under voltage release - 110 V a.c derived from P.T<br />

Shunt trip coil - 24 V d.c<br />

Safety interlock 7 locking facility – Required<br />

……………………………………………………………………<br />

2.1 Metering: Digital TVM for measuring power parameters,<br />

energy, harmonic parameters etc.,. with SNMP / RS 485 output<br />

interface. Software for remote M&C shall be supplied.<br />

Make: Satec. Model : PM 130 EH<br />

Analog Voltmeter, Size: 96 x 96 with selector switch<br />

Max. demand type Analog Ammeter ; Size: 96 x 96 with selector<br />

switch<br />

Phase sequence meter Size: 96 x 96 with selector switch<br />

……………………………………………………………………<br />

2.2 Protection Relay: Microprocessor based transformer<br />

protection relay with SNMP / RS 485 output interface.<br />

Features: 3 PHASE OVER CURRENT, EARTH FAULT RELAY +<br />

THERMAL FOR TRANSFORMER, 20-110V AC/DC<br />

Device code: 50/51, 46, 49<br />

Design: Numeric<br />

Functions: Low set and High set Over current<br />

Low set and High set Earth Fault with site selectable Trip<br />

characteristics, Definite inverse time tripping Thermal overload.<br />

Display of parameters, built in self supervision, RS 485 Port<br />

communication<br />

Make: L&T, Model: IM 30 T<br />

Software for remote M&C shall be supplied.<br />

……………………………………………………………………<br />

2.3 Master trip relay: High speed Relay with manual reset<br />

Type VAJH 13, Alstom make<br />

………………………………………………………………….<br />

2.4 Metering & protection CT's - Resin cast dry type<br />

Single phase, 2 core<br />

Ratio – 75-150/ 5 - 5 A<br />

Core - 1: Class - 1.0 15 VA<br />

Core II - Class 5P10, 15 VA<br />

Suitable for STC of 26.3 kA for 1 sec<br />

…………………………………………………………………….<br />

VCB BOM<br />

mentioned<br />

Sl 2.0 to<br />

2.11 is for<br />

individual<br />

VCB<br />

modules<br />