Master Control Facility – Hassan<br />

33<br />

34<br />

35<br />

36<br />

37<br />

Cable Ducts<br />

Manufactured from high impact rigid PVC, should not peel, chip or break, non<br />

inflammable, warp proof, non-britle, high di-electric strength (36 kV / mm),<br />

Temperature withstand capacity up to 70 degree C, Colour: Grey, Type B<br />

locking, width & deapth of the duct shall be selected according to the<br />

requirement and shall be uniform in size. Make: Salzer / Connectwell / Wago<br />

/ Elmex / Lapp<br />

Cable Ties<br />

Re-usable type, white coloured, Nylon cable ties, Length of the ties selected<br />

according to the requirement. Make: Any Reputed make<br />

Ferrules / Stickers<br />

Ferrules of suitable type, size shall be selected for each cable on both sides<br />

and for terminal blocks. Laminated stickers for marking Circuit breakers /<br />

SDFUs / Fuse links / Terminal blocks shall fixed as per the standard<br />

configuration<br />

Lugs<br />

Suitable insulated coloured heavy duty lugs made of tinned copper shall be<br />

used for control cable / SDFU upto 63A / MCB input output cable terminations<br />

as per the cable size. Make: Dowells/Multi/3D/Jainson<br />

High purity electrolyte Aluminium Busbars<br />

Rating: 2.0 MVA for main busbar, Aluminium bus bar complying to IS 5082<br />

1981, 63401-WP, suitable size and rating for vertical busbar system, suitabl<br />

size Busbar shall be selected for tapping from buabar to switchgears &<br />

switchgear to termination ends, The busbar thickness shall not be more than<br />

8 mm<br />

As<br />

required<br />

As<br />

required<br />

As<br />

required<br />

As<br />

required<br />

MS items, Fabrication, Insulators, Painting, Wiring and Testing as per the<br />

38<br />

enclosed technical specification enclosed.<br />

39 Sub-Total A<br />

B LV Busduct Indoor / Outdoor System<br />

40<br />

LV Busduct System<br />

Non-segregated, bus ducts having 3 phase & neutral busbars housed in a<br />

common Galvanized zinc sheet metallic enclosure. Degree of protection -<br />

IP54, Outdoor from Transformer (1MVA) to inside the building & Indoor from<br />

building to LT panel. Rating 415V, 2000A , Busbar material -Aluminium,<br />

complying to IS 5082 1981, 63401-WP. Short circuit withstand capacity -50<br />

kA (rms) for 1 sec, Confirming to IEC 439-2, IS-8623-2, Insulation material -<br />

Multi layer class F (155 degree) insulation, Earth busbar -Upto 50 % of<br />

phase cross section can be fitted outside, Enclosure material -1.6 mm CRCA<br />

with epoxy polyester powder coating, Standard accessories to be used as per<br />

the system requirement like, bends, expansion joints, flexible link, phase<br />

cross over, rubber bellow, marshalling cabinet, adopter at transformer and<br />

panel end & wall frame. The exact length of indoor, outdoor bus duct may be<br />

taken at site during panel fabrication.<br />

40a Indoor (15 meters approximately)<br />

40b Outdoor (20 meters approximately)<br />

R Meter<br />

R Meter<br />

Semi Modular substation LT panel –Specification 14