Master Control Facility – Hassan<br />

15<br />

16<br />

17<br />

18<br />

19<br />

20<br />

Ultra Safe Modular Fuse Holders (For DC control circuits)<br />

Single pole, Suitable for 14x51 cylindrical HRC fuse links, Din rail mounting<br />

type, Confirming to IEC 269-2-1, 'Finger safe' under IEC standards to an IP-2<br />

grade of protection, Blown fuse indicators for each pole. Make; Siemens /<br />

Schneider / Ferraz-Shamutt / Telemecanique<br />

HRC Fuse Links (For DC control circuit)<br />

Rating: 4A, Nominal Voltage: 415VAC, Breaking capacity: 80kA at 415VAC,<br />

P.F. of 0.15, Confirming to IS: 9224 1979. Cylindrical type of size 14 x 51<br />

mm. Make: Siemens / Schneider / Ferraz-Shamutt / Telemecanique<br />

CT Shorting isolator (for T1, T2, G1, G2 & G3 -Satec meter)<br />

Triple pole isolator, Rating: 16A. Make: L&T -Hager / Siemens / Schneider /<br />

MDS -Legrand / GE / ABB<br />

CT Shorting Terminals (for LT panel outgoing feeders)<br />

Terminal connector, 800 VAC grade, Suitable for termination of cable from<br />

0.08 to 4 sq mm, Rating -32A, Colour -Grey, Din rail mounting type, Material<br />

-modified Nylon 6.6 free of halogens, flurocarbons etc., Continuous operating<br />

temperature -105 degree C, Electrolytic copper Ecu. Make: WAGO or<br />

equivalent in Connectwell / Salzer<br />

Change Over, ON / OFF, Auto / Manual Switch<br />

(For Neutral contactor, PSI) Rating: 10A, Switching angle 90 degree, Flush<br />

mounting type, Rated operational voltage -440VAC, Frame size -48 mm.<br />

Make: L&T-Salzer / Kaycee / Siemens / Schneider<br />

Breaker Control Switch (TNC)<br />

Frame size - 88 mm, Lever handle, shall be lockable in neutral position, Front<br />

mounting with grey colour, handle black colour, Engraved 'Trip', Neutral' &<br />

'Close', IP 40 protection. Make: L&T-Salzer / Kaycee / Siemens / Schneider<br />

25<br />

25<br />

5<br />

As<br />

required<br />

As<br />

required<br />

9<br />

21<br />

22<br />

23<br />

24<br />

Power Contactor (For G1, G2 & G3 Neutral)<br />

Utilization category AC-3 at 415 V, 50 Hz, 3 Ph, Auxiliary contact 2NO+2NC, Coil<br />

voltage: 240 VAC, Confirming to IS13947 (Part 4 / Sec.1) and IEC 60947-4-1,<br />

Rating: 400A, Rated insulation voltage: 690V AC. Make: L&T / Schneider -TM /<br />

Siemens / ABB<br />

Emergency Push button<br />

The local EPO shall include a non-illuminated "Emergency Power Off"<br />

pushbutton. Pressing the EPO switch shall immediately shut down the unit by<br />

activating the shunt trip of the all main input and bus coupler circuit breakers.<br />

Make: L&T-ESBEE / Siemens / Schneider / ABB / Tecnic<br />

Flasher with beeper / Indicator banks (For T1, T2, G1 to G3)<br />

Amber colour flasher cum beeper for fault trip indication & alarm with<br />

acknowledgement. Make: MIMIC / Schneider / Rittal<br />

Indicating Lamps<br />

(For T1, T2, G1, G2, G3 RYB indicatios, ACBs ON/OFF indications, Fault trip<br />

indications) Type: LED, Ribbed lens with trim collar anodised bright, Flush<br />

head, Input supply voltage 250VAC, 50 Hz. Color cade should be Red,<br />

Yellow, Blue & Green. Make: L&T-ESBEE / Siemens / Vaishnav / Tecnic /<br />

Schneider / ABB<br />

3<br />

1<br />

5<br />

As<br />

required<br />

Semi Modular substation LT panel –Specification 12