DESIGN PARAMETERS:<br />

Given below are some design parameters which should be followed in addition to those given in<br />

various sections of technical specifications enclosed.<br />

a) Temperature of chilled water entering the chiller ºC : 12.22<br />

b) Temperature of chilled water leaving the chiller ºC : 6.67<br />

c) Fouling factor of chiller (MKS) : 0.0001<br />

d) Air Inlet temperature to condenser ºC : 43.3<br />

AIRHANDLERS:<br />

a) Maximum Face velocity across cooling coil MPM : 152.0<br />

b) Maximum face velocity across all types of filter MPM : 152.0<br />

c) Maximum water pressure drop across the coil in Mt. : 4.6<br />

d) Maximum water velocity through coil in MPS : 2.5<br />

e) Fan outlet velocity (maxm.) MPS : 12.0<br />

f) Fan Speed (maxm.) of air h<strong>and</strong>ing unit RPM : 1000<br />

FAN COIL UNITS:<br />

a) Maximum Face velocity across cooling coil MPM : 152.0<br />

b) Maximum face velocity across prefilters MPM : 152.0<br />

c) Maximum water pressure drop across the coil in Mt. : 4.6<br />

d) Maximum water velocity through coil in MPS : 2.5<br />

e) Fan outlet velocity (maxm.) MPS : 12.0<br />

DUCTING WORK:<br />

a) Method of Duct Design : Equal Friction Method<br />

b) Maximum air velocity in supply duct MPM : 460.0<br />

c) Maximum air velocity in return duct MPM : 305.0<br />

d) Friction loss in duct (maxm.) MM Wg in 100 Mt run. : 8.33<br />

e) Maximum Velocity at supply air grill outlet MPM : 150.00<br />

PIPING WORK:<br />

a) Friction loss (maxm.) Mt / 30 Mt length : 1.60<br />

b) Flow velocity (maxm.) Mt / Sec. : 2.50<br />

INSULATION:<br />

Maximum temperature rise in the supply air duct from<br />

air h<strong>and</strong>lers outlet to farthest outlet in ºC : 1.10