52. Code of practice <strong>for</strong> installation <strong>and</strong> maintenance<br />

of motors<br />

IS 3106 : 1966<br />

53. Bourden tube pressure <strong>and</strong> vacuum gauges IS : 3624<br />

54. Code of practice <strong>for</strong> selection of st<strong>and</strong>ard worm<br />

<strong>and</strong> helical gear boxes.<br />

55. Mild tubes, tubulars <strong>and</strong> other wrought steel<br />

fittings.<br />

56. Electrically welded steel pipes <strong>for</strong> water, gas <strong>and</strong><br />

sewage.<br />

57. Gun metal gate, globe <strong>and</strong> check valves <strong>for</strong><br />

general purposes.<br />

IS : 7403<br />

IS : 1239<br />

IS : 3589<br />

IS : 778<br />

NOISE AND VIBRATION CONTROLS:<br />

The air conditioning contractor must take all necessary precautions to have minimum noise<br />

generation <strong>and</strong> its transmission. Minimum vibration as permitted by IS relevant code shall be<br />

ensured. A few points <strong>for</strong> guidance only are given below:<br />

a) Double fire retardant flexible connections shall be provided from air discharge to outlet of airh<strong>and</strong>ler<br />

to the duct.<br />

b) Vibration isolation pads of suitable thickness commensurate to loading <strong>for</strong> isolation of vibration<br />

shall be provided under all pumps, air h<strong>and</strong>lers fans etc. in consultation with manufacturer <strong>for</strong><br />

proper selection of vibration isolators.<br />

c) Vibration isolation springs of suitable size to suit the weight of Air Cooled chilling machine if<br />

recommended by the manufacturer <strong>for</strong> elimination of vibrations shall be provided as suitable <strong>for</strong><br />

type <strong>and</strong> model of Air Cooled chilling unit.<br />

d) The floor supported piping shall be mounted on pipe supports with 7.5mm ribbed neoprene pads<br />

between the base plate of the pipes <strong>and</strong> the floors.<br />

e) In case of ducts, conduits, pipes <strong>and</strong> tubes the annular space between construction <strong>and</strong><br />

penetrating element shall be sealed suitably.<br />

f) All ducts starting from air h<strong>and</strong>ling unit shall be provided with acoustic lining as indicated in the<br />

tender drawings.<br />

g) The air-conditioning contractor shall take all other precautions or shall make his own<br />

arrangements even if not specified in the tender documents <strong>for</strong> eliminating high noise levels<br />

<strong>and</strong> shall minimize vibrations in all mechanical equipments without any additional cost.<br />

INDIGENOUS SCROLL AIRCOOLED CHILLERS:<br />

The specification under this section covers the supply, installation, testing <strong>and</strong> commissioning of the<br />

INDIGENOUS AIRCOOLED CHILLERS con<strong>for</strong>ming to these specifications <strong>and</strong> in accordance with<br />

the requirements of the schedule of equipment.