52. Code of practice <strong>for</strong> installation <strong>and</strong> maintenance<br />
of motors<br />
IS 3106 : 1966<br />
53. Bourden tube pressure <strong>and</strong> vacuum gauges IS : 3624<br />
54. Code of practice <strong>for</strong> selection of st<strong>and</strong>ard worm<br />
<strong>and</strong> helical gear boxes.<br />
55. Mild tubes, tubulars <strong>and</strong> other wrought steel<br />
fittings.<br />
56. Electrically welded steel pipes <strong>for</strong> water, gas <strong>and</strong><br />
sewage.<br />
57. Gun metal gate, globe <strong>and</strong> check valves <strong>for</strong><br />
general purposes.<br />
IS : 7403<br />
IS : 1239<br />
IS : 3589<br />
IS : 778<br />
NOISE AND VIBRATION CONTROLS:<br />
The air conditioning contractor must take all necessary precautions to have minimum noise<br />
generation <strong>and</strong> its transmission. Minimum vibration as permitted by IS relevant code shall be<br />
ensured. A few points <strong>for</strong> guidance only are given below:<br />
a) Double fire retardant flexible connections shall be provided from air discharge to outlet of airh<strong>and</strong>ler<br />
to the duct.<br />
b) Vibration isolation pads of suitable thickness commensurate to loading <strong>for</strong> isolation of vibration<br />
shall be provided under all pumps, air h<strong>and</strong>lers fans etc. in consultation with manufacturer <strong>for</strong><br />
proper selection of vibration isolators.<br />
c) Vibration isolation springs of suitable size to suit the weight of Air Cooled chilling machine if<br />
recommended by the manufacturer <strong>for</strong> elimination of vibrations shall be provided as suitable <strong>for</strong><br />
type <strong>and</strong> model of Air Cooled chilling unit.<br />
d) The floor supported piping shall be mounted on pipe supports with 7.5mm ribbed neoprene pads<br />
between the base plate of the pipes <strong>and</strong> the floors.<br />
e) In case of ducts, conduits, pipes <strong>and</strong> tubes the annular space between construction <strong>and</strong><br />
penetrating element shall be sealed suitably.<br />
f) All ducts starting from air h<strong>and</strong>ling unit shall be provided with acoustic lining as indicated in the<br />
tender drawings.<br />
g) The air-conditioning contractor shall take all other precautions or shall make his own<br />
arrangements even if not specified in the tender documents <strong>for</strong> eliminating high noise levels<br />
<strong>and</strong> shall minimize vibrations in all mechanical equipments without any additional cost.<br />
INDIGENOUS SCROLL AIRCOOLED CHILLERS:<br />
The specification under this section covers the supply, installation, testing <strong>and</strong> commissioning of the<br />
INDIGENOUS AIRCOOLED CHILLERS con<strong>for</strong>ming to these specifications <strong>and</strong> in accordance with<br />
the requirements of the schedule of equipment.