) Exp<strong>and</strong>ed Polystyrene<br />

The density of exp<strong>and</strong>ed polystyrene shall not be less than 20 kg per cubic meter <strong>and</strong> the thermal<br />

conductivity shall not exceed 0.031 Kcal./ hr.m °C at 10 °C mean temperature.<br />

The sample of insulation material shall be submitted <strong>for</strong> approval to the Engineer in Charge <strong>and</strong> the<br />

sample shall be tested <strong>for</strong> thermal conductivity values by the contractor at his own expense. Adhesive<br />

used <strong>for</strong> setting the insulation shall be non-flammable, vapour proof, CPRX compound.<br />

INSULATION ON SHEET METAL DUCTING<br />

The thickness of insulation used on ducting shall be as detailed below:<br />

Conditioned space<br />

a) <strong>Supply</strong> Air Duct Insulated with factory Pre-laminated 25mm thick Fibre Glass as shown in the<br />

tender drawing.<br />

b) Return Air Insulated with factory Pre-laminated 25mm thick Fibre Glass as shown in the<br />

tender drawing.<br />

c) Fresh Air Duct Insulated with factory Pre-laminated 25mm thick Fibre Glass as shown in the<br />

tender drawing.<br />

d) Plenums Lined internally with 25mm thick fiberglass rigid board as shown in the<br />

tender drawing.<br />

e) FCU Collars Lined internally with 12 mm thick fiberglass rigid board as shown in the<br />

tender drawing.<br />

The application of insulation should be carried out in workman like manner as detailed below.<br />

INSULATION OF DUCTING WITH ALUMINUM FACED FIBERGLASS:<br />

a) Duct surface to be cleaned thoroughly<br />

b) To apply two coats of CRPX compound.<br />

c) To fix factory pre-laminated aluminum faced fibre glass insulation of density 24 Kg/cmt of specified<br />

thickness.<br />

d) Fix self-adhesive aluminum tape of 50 mm width on all longitudinal / transverse joints.<br />

e) Finally fix PVC straps of 25mm width at every 300mm centre to centre.<br />

ACOUSTIC LINING OF DUCT:<br />

The material to be used <strong>for</strong> duct lining shall be 12 / 25mm thick resin bonded fibre glass rigid board<br />

having a density of 48 Kg/m³ <strong>and</strong> covered with 0.5 mm thick per<strong>for</strong>ated aluminum sheet. The lining of<br />

initial length of the duct shall be done as shown in the tender layout drawings & shall be carried out as<br />

follows.<br />

a) Clean the duct piece thoroughly,<br />

b) Fix the board of suitable thickness inside the duct <strong>and</strong> cover with fibre glass tissue paper.<br />

c) Cover the insulation board with 0.5mm thick per<strong>for</strong>ated aluminum sheet with at least 20%<br />

per<strong>for</strong>ation.<br />

d) Secure the insulation board <strong>and</strong> aluminum sheet with cadmium coated bolts nuts <strong>and</strong> cup washers<br />

/ steel screws.<br />

e) Finally seal the ends completely, so that no lining material is exposed.<br />