a) Double fire retardant Canvass Connection.<br />
b) 12 mm thick cleanable aluminum filters with aluminum frame.<br />
c) Strainer with ball valve at inlet & ball valve at outlet.<br />
d) Balancing valve in return chilled water line.<br />
e) Copper connections between chilled water lines, controls etc.<br />
f) Electrical wiring between motors.<br />
It may be noted that all accessories specified above shall be provided along with the Fan Coil Unit<br />
<strong>and</strong> shall be included in the price of Fan Coil Unit.<br />
Each Fan Coil Unit shall be tested at factory <strong>and</strong> complete in all respects. The sound level of the unit<br />
should not exceed 40 dB. The test certificate shall be furnished with each Coil Unit. It is necessary to<br />
design the fan coil unit in a way to have silent operation. The Fan Coil Unit shall be powder coated<br />
both internally <strong>and</strong> externally.<br />
DESIGN PARAMETERS OF FAN COIL UNITS:<br />
The design parameters of Fan Coil Units are given below:<br />
FAN COIL UNIT - CEILING SUSPENDED:<br />
a) Capacity<br />
b) Air quantity CMH<br />
c) Fan Static pressure<br />
d) Face area of cooling Coil (SMT) minimum<br />
e) No. of fins / cm<br />
f) No. of rows deep<br />
1.0TR 1.5 TR 2.0 TR 2.5 TR 3.0 TR<br />
680 1020 1360 1700 2040<br />
------------------------- 10MM-------------------------<br />
0.129 0.17 0.23 0.293 0.325<br />
---------------------------- 4.70 -------------------------<br />
3 3 4 4 4<br />
g) Motor HP (Single Phase) ----------------- To suit the requirement ------------------<br />
h) 22 G SS Insulated tray -----------------------------YES ---------------------------------<br />
i) Type of painting ----------------------Powder coated finish only-------------<br />
TESTING:<br />
The fan coil units shall be tested as per Per<strong>for</strong>ma Test Readings.<br />
THERMAL / ACOUSTIC INSULATION:<br />
This section deals with supply <strong>and</strong> fixing of thermal / acoustic insulation of ducts, pipes etc. as per<br />
the specification given in this section.<br />
MATERIAL OF INSULATION:<br />
The insulation material of the following kind shall be used <strong>for</strong> cold insulation.