All starters shall be provided with thermal over load relay.<br />

All star delta starters shall have adjustable timers.<br />

Rating of motors shall be selected to suit the application as indicated in the Schedule of Equipment.<br />

All starters shall be provided as specified in Bill of Quantities. All starter shall be compatible to the<br />

drive <strong>and</strong> driven equipment.<br />

Auxiliary contacts <strong>for</strong> interlocking purpose shall be provided in the starter.<br />

INSTALLATION OF MOTORS:<br />

The motor <strong>and</strong> drive machine shall be fixed on slide rails to facilitate belt <strong>and</strong> other adjustments.<br />

Vibration isolation arrangement shall be provided.<br />

The installation of motor shall be carried out as per IS:900.<br />

The motor with driving equipment shall be mounted on foundation <strong>and</strong> connected to each other with<br />

flexible coupling with guard in condenser <strong>and</strong> chilled water pumps.<br />

All motors after installation shall be tested at site <strong>for</strong> vibrations, heating <strong>and</strong> electrical insulation<br />

resistance by AC contractor.<br />

MOTOR CONTROL CENTRE (MV PANEL), AHU SUB-PANEL:<br />

This section deals with supply, installation, testing <strong>and</strong> commissioning of Motor Control Centre (MV<br />

panel), AHU Sub-Panels etc. <strong>and</strong> shall be manufactured by CPRI approved venders. The power /<br />

control cabling <strong>and</strong> earthing work shall be carried out as per the specification given below:<br />

SCOPE:<br />

All work shall confirm to Indian Electricity Act (amended upto date), I.S. code of practices local rules<br />

<strong>and</strong> regulations etc. Power cabling shall be carried out with approved make of cables as indicated in<br />

the List of approved make of equipment / materials <strong>and</strong> shall be of grade 1100 volts, PVC<br />

insulated <strong>and</strong> sheathed, armoured aluminum conductors cables. Control cabling shall be of approved<br />

make <strong>and</strong> shall be of grade 1100 volts, PVC insulated & sheathed, copper conductor armoured<br />

multicore cables as specified in BOQ.<br />

MOTOR CONTROL CENTRE (MV PANEL) / AHU SUB-PANEL:<br />

Motor control centre (MV Panel) floor mounted extendable type <strong>and</strong> wall mounted AHU sub-panel<br />

shall be fabricated out of 14G C.R.C.A. Sheet. These panels shall be cubical sectionalised type,<br />

totally enclosed dust & vermin proof. Gaskets shall be provided in all joints to prevent dust to reach<br />

the internals of the panels to make it completely dust proof.<br />

The degree of protections <strong>for</strong> panels shall be IP 52 <strong>for</strong> indoor applications <strong>and</strong> IP 55 <strong>for</strong> outdoor<br />

applications as per IS:2147.<br />

This panel (MV) shall be suitable <strong>for</strong> voltages upto 500 volts, three phase 50 Hz, 4 wire supply<br />

capable of functioning satisfactorily in temperature ranging up to 45 to 50 degree centigrade <strong>and</strong><br />

rupturing capacity suitable <strong>for</strong> connected load <strong>and</strong> design should be type tested <strong>for</strong> 42 KA fault level.<br />

All joints of panels shall be welded <strong>and</strong> braced as necessary to provide a rigid support <strong>for</strong> all<br />

components. The base channel provided in the floor mounted MV panel shall be 75mm high <strong>and</strong> a<br />

clear space of 200mm between the floor <strong>and</strong> the bottom most part of the unit shall be provided. The<br />

panel shall be correctly positioned. Self- threading screws shall not be used in the construction of<br />

control panels.<br />

No of Corrections<br />