<strong>Transmission</strong> to Un-bottle Staten Island Generation<br />

Project to Address Potential Indian Point/Downstate Generation Retirement<br />

Project Description:<br />

Un-bottling Staten Island generation resources will occur in two phases. Phase 1 would mitigate a<br />

contingency within <strong>New</strong> <strong>York</strong> City by separating a common pipe double leg feeder into two separate<br />

feeders with independent positions at the Goethals and Linden Substations. Phase 2 increases<br />

transmission capacity by adding forced cooling to existing feeders between Goethals, Gowanus, and<br />

Farragut. The Project would be located in Staten Island and Brooklyn, <strong>New</strong> <strong>York</strong> and Union County<br />

(Linden), <strong>New</strong> Jersey. This project is located entirely in NYISO Zone J.<br />

Project Size:<br />

Phase 1: The length of the feeder, operating voltage level (345 kV) and ratings would not change.<br />

However the cables will be able to carry an additional of 280MW.<br />

Phase 2: The length of the feeders, operating voltage level (345 kV) would not change but the ratings<br />

would increase by 200 MW.<br />

Total Project Size: 480 MW<br />

Terminal Stations and required upgrades:<br />

The terminal stations are:<br />

1) Goethals 345 kV substation where a bus position needs to be established for the feeder separation.<br />

2) Linden 345 kV substation where a bus position needs to be established for the feeder separation.<br />