Dew Cell Dew Point Probe (P/N 203-1902)<br />

Overview<br />

The dew cell dew point probe can be used to monitor<br />

the dew point of a particular area. The probe should be<br />

mounted in a relatively dust free area with the probe in an<br />

“up” position.<br />

Mounting<br />

The dew cell dew point probe should be located four to<br />

six feet from the floor with the probe pointing up. An area<br />

with minimum exposure to dust is recommended.<br />

Mount the probe using the st<strong>and</strong>ard switch cover supplied<br />

with the unit, as shown in Figure 15.<br />

Figure 15 -Dew Cell Dew Point Probe Mounting<br />

Wiring<br />

Wire the Dew Cell Dew Probe to the 16AI board as<br />

shown in Figure 16.<br />

1. Wire the black lead to an odd-numbered terminal.<br />

2. Wire the red leads to even-numbered terminal.<br />

3. Wire the green lead to AC1.<br />

4. Wire the white lead to AC2.<br />

5. Make sure the corresponding Input Dip<br />

Switch is UP.<br />

<strong>Peripherals</strong> Manual Dew Cell Dew Point Probe (P/N 203-1902) • 19