Eclipse Pressure Transducers<br />

0–100 PSIG–P/N 800-1100<br />

0–200 PSIG–P/N 800-1200<br />

0–500 PSIG–P/N 800-1500<br />

Overview<br />

Do NOT connect an Eclipse ® Pressure Transducer to<br />

a 12V supply. Eclipse ® transducers are rated for 5V<br />

DC.<br />

<strong>CPC</strong> supplies Eclipse ® Pressure Transducers for use in<br />

some refrigeration control systems. All 100, 200, <strong>and</strong> 500<br />

PSIG pressure transducers ordered for use with RMCC systems<br />

or shipped with new RMCC systems will be Eclipse ®<br />

transducers.The part numbers <strong>and</strong> hardware specifications<br />

are listed in Table 8. Software setup is described below.<br />

Part Number 800-1100 800-1200 800-1500<br />

Pressure<br />

Range<br />

Max Overload<br />

PSIG<br />

(w/o Damaging<br />

xducer)<br />

Max Overload<br />

PSIG<br />

(w/o Bursting)<br />

Description<br />

0 - 100<br />

PSIG<br />

0 - 200<br />

PSIG<br />

0 - 500<br />

PSIG<br />

200 PSIG 400 PSIG 750 PSIG<br />

500 PSIG 1000 PSIG 2500 PSIG<br />

Excitation +5 VDC ±0.25 V, 20 mA max<br />

Accuracy ±1% Span from best fit straight line. Includes<br />

effects of non-linearity, hysteresis,<br />

<strong>and</strong> repeatability.<br />

Operating &<br />

Storage Temperature<br />

Range<br />

Compensated<br />

Temperature<br />

Range<br />

-40° F to 221° F<br />

(-40° C to 105° C)<br />

-0° F to 180° F<br />

(-18° C to 82° C)<br />

Total Error ±4% of full scale. Includes effects of<br />

temperature, non-linearity, hysteresis,<br />

<strong>and</strong> repeatability.<br />

Table 8-Specifications for Eclipse ® Pressure Transducers<br />

The Eclipse ® pressure transducer is a pressure-sensing<br />

device that converts pressure readings to a proportional<br />

electrical signal between 0.5 - 4.5 volts DC. The transducer<br />

is designed with a 1/8” male national pipe thread (NPT) fitting<br />

for connection to a st<strong>and</strong>ard access fitting.<br />

If the access fitting is configured with a Schrader valve,<br />

this fitting will have to be replaced with a st<strong>and</strong>ard 1/8”<br />

NPT female fitting. Each transducer is supplied with 20<br />

feet of cable for connection to a 16AI input board. Table 9-<br />

shows pressure/voltage ranges for each transducer.<br />

<strong>Peripherals</strong> Manual Eclipse Pressure Transducers • 33