Eclipse Pressure Transducers<br />
0–100 PSIG–P/N 800-1100<br />
0–200 PSIG–P/N 800-1200<br />
0–500 PSIG–P/N 800-1500<br />
Overview<br />
Do NOT connect an Eclipse ® Pressure Transducer to<br />
a 12V supply. Eclipse ® transducers are rated for 5V<br />
DC.<br />
<strong>CPC</strong> supplies Eclipse ® Pressure Transducers for use in<br />
some refrigeration control systems. All 100, 200, <strong>and</strong> 500<br />
PSIG pressure transducers ordered for use with RMCC systems<br />
or shipped with new RMCC systems will be Eclipse ®<br />
transducers.The part numbers <strong>and</strong> hardware specifications<br />
are listed in Table 8. Software setup is described below.<br />
Part Number 800-1100 800-1200 800-1500<br />
Pressure<br />
Range<br />
Max Overload<br />
PSIG<br />
(w/o Damaging<br />
xducer)<br />
Max Overload<br />
PSIG<br />
(w/o Bursting)<br />
Description<br />
0 - 100<br />
PSIG<br />
0 - 200<br />
PSIG<br />
0 - 500<br />
PSIG<br />
200 PSIG 400 PSIG 750 PSIG<br />
500 PSIG 1000 PSIG 2500 PSIG<br />
Excitation +5 VDC ±0.25 V, 20 mA max<br />
Accuracy ±1% Span from best fit straight line. Includes<br />
effects of non-linearity, hysteresis,<br />
<strong>and</strong> repeatability.<br />
Operating &<br />
Storage Temperature<br />
Range<br />
Compensated<br />
Temperature<br />
Range<br />
-40° F to 221° F<br />
(-40° C to 105° C)<br />
-0° F to 180° F<br />
(-18° C to 82° C)<br />
Total Error ±4% of full scale. Includes effects of<br />
temperature, non-linearity, hysteresis,<br />
<strong>and</strong> repeatability.<br />
Table 8-Specifications for Eclipse ® Pressure Transducers<br />
The Eclipse ® pressure transducer is a pressure-sensing<br />
device that converts pressure readings to a proportional<br />
electrical signal between 0.5 - 4.5 volts DC. The transducer<br />
is designed with a 1/8” male national pipe thread (NPT) fitting<br />
for connection to a st<strong>and</strong>ard access fitting.<br />
If the access fitting is configured with a Schrader valve,<br />
this fitting will have to be replaced with a st<strong>and</strong>ard 1/8”<br />
NPT female fitting. Each transducer is supplied with 20<br />
feet of cable for connection to a 16AI input board. Table 9-<br />
shows pressure/voltage ranges for each transducer.<br />
<strong>Peripherals</strong> Manual Eclipse Pressure Transducers • 33