04.10.2014 Views

Chilled Beam Design Guide - TROX

Chilled Beam Design Guide - TROX

Chilled Beam Design Guide - TROX

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Airside <strong>Design</strong> Considerations<br />

Space temperature control in passive beam systems is<br />

accomplished by varying the amount of sensible heat<br />

removed by the chilled water. The chilled water supply<br />

to several beams within a single zone is generally<br />

controlled by a single chilled water valve. Although the<br />

zone may consist of multiple spaces, a certain degree<br />

of temperature compensation for each space will be<br />

affected by the passive beam itself. As the cooling<br />

requirement of the space is reduced, the temperature of<br />

the air entering the beam will also be reduced. This will<br />

result in less heat transfer to the water circuit and a<br />

lower return water temperature.<br />

Passive chilled beams cannot be used for heating as its<br />

airflow would be reversed. They are typically applied<br />

with some type of separate heating system such as low<br />

level finned tube heaters. Radiant (ceiling or wall<br />

mounted) heating panels can also be used depending<br />

on the façade heat losses expected.<br />

Thermal comfort considerations with active beams<br />

While the primary (conditioned) airflow rate for active<br />

chilled beams can be greatly reduced, their induction<br />

ratios (2 to 6 CFM of room air per CFM primary air)<br />

result in discharge airflow rates that are slightly higher<br />

than those of conventional all-air systems. As such,<br />

attention should be exercised in the beam placement to<br />

avoid drafty conditions and maximize occupant thermal<br />

comfort. Figure 19 predicts maximum occupied zone<br />

velocities for various combinations of primary airflow<br />

rates and active beam spacing. This nomograph<br />

suggests local velocities which will maintain acceptable<br />

levels of occupant comfort per ASHRAE.<br />

Active beams can be for heat in moderate climates. Hot<br />

water can either be delivered to each perimeter area<br />

beam or to a hot water heating coil in the duct supplying<br />

a number of beams within the same thermal control<br />

zone. The use of a zone hot water heating coil feeing<br />

multiple chilled beams is a generally more economic<br />

option than piping each chilled beam for heating as it<br />

may save considerable labor and piping material costs.<br />

If active chilled beams are used for heating, the following<br />

recommendations should be observed:<br />

• <strong>Chilled</strong> beam discharge temperatures should<br />

be maintained within 15˚F of the room<br />

temperature.<br />

• Velocities at the mid-level of outside walls and<br />

windows should be maintained within the<br />

region indicated in figure 19.<br />

Unoccupied periods demanding heating via the chilled<br />

beams or primary air system will require that the AHU<br />

remain operational.<br />

Variable air volume operation using active beams<br />

Although normally operated as constant air volume<br />

delivery devices, active chilled beams can also be used<br />

as variable air volume (VAV) devices. VAV operation<br />

may be advantageous when space occupancy and/or<br />

ventilation demands vary widely. Recommendations for<br />

the control of chilled beams in VAV applications can be<br />

found in the control section of this document.<br />

As the room air distribution provided by active<br />

beams is identical to that provided by ceiling slot<br />

diffusers, their selection for (total) discharge airflow<br />

rates greater than 40 CFM per linear foot of slot is<br />

not recommended when high levels of occupant<br />

thermal comfort are required!<br />

The v L velocities shown in figure 19 are those predicted<br />

within 2 inches of the window or wall surface during<br />

cooling operation. It is recommended that beams which<br />

are configured for both heating and cooling of perimeter<br />

spaces be selected such that v L (selected for cooling<br />

operation) is between 120 and 150 FPM in order to<br />

assure that the warm air is adequately projected down<br />

the perimeter surface. Velocities taken 6 inches away<br />

from the surface can be expected to be about half those<br />

values.<br />

Heating in chilled beam applications<br />

Ceiling or high sidewall mounted passive chilled beams<br />

exert no motive force on their discharge airflow, and<br />

cannot be used for overhead heating. Heating must be<br />

provided by a separate source, either the primary air<br />

supply or a separate heating system (finned tube,<br />

radiant panel, etc.).<br />

17

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!