PRIMARY AIR COOLING<br />

Net Sensible Heating Capacity, BTUH/LF<br />

WATER SIDE HEATING<br />

NET SENSIBLE HEATING<br />

Heating Performance (4-Pipe) DID622<br />

1000<br />

900<br />

800<br />

Chart is based on 6 ft. DID622-US-4 or<br />

DID622-HC-4 (4 pipe) heating with a 20˚F<br />

temperature differential between room<br />

and primary air and an 50˚F temperature<br />

differential between room and entering<br />

hot water. For other beam lengths, see<br />

the correction factors table below.<br />

GPMHWS<br />

700<br />

GPMHWS<br />

1.5<br />

1.0<br />

600<br />

1.5<br />

0.8<br />

500<br />

400<br />

1.0<br />

0.8<br />

0.6<br />

0.6<br />

0.4<br />

300<br />

0.4<br />

0.3<br />

0.3<br />

200<br />

0.2<br />

100<br />

0.2<br />

0<br />

-100<br />

-200<br />

-300<br />

NC<br />

15 20 25 27<br />

-400<br />

0.2" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"M" NOZZLES<br />

-500<br />

"G" NOZZLES<br />

NC<br />

15<br />

20<br />

25 30 35 37<br />

0.2"<br />

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"<br />

1.0"<br />

2.0<br />

4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID622-US-4 or DID622-HC-4 Lengths & T ENTERING WATER - T INDUCED AIR<br />

Performance Parameter<br />

Water Side Heating (BTUH/LF)<br />

Max. Recommended GPM (DID622-US-4 models)<br />

Max. Recommended GPM (DID622-HC-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.03 No Correction Multiply by 0.96 Multiply by 0.92<br />

1.5 1.5 1.5<br />

1.5<br />

1.5 1.5 1.5<br />

1.5<br />

-5 No Correction +3<br />

+6<br />

Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.97<br />

Hot Water Pressure Loss See Figure 41 36<br />

TENTERING HOT WATER - TINDUCED AIR<br />

See Table 7 (page 38)<br />

Figure 56: 51: Heating (4 Pipe) Performance, DID622-US-4 and DID622-HC-4<br />

55