Sensible Cooling Capacity, BTUH/LF<br />

PRIMARY AIR COOLING SECONDARY (WATER) COOLING<br />

TOTAL SENSIBLE COOLING<br />

Cooling Performance (2-Pipe) DID602<br />

1600<br />

1500<br />

1400<br />

Chart is based on 6 ft. DID602-HC-2 (2<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

GPM CWS<br />

1300<br />

Performance at water flow rates > 1.5<br />

GPM is only achievable with DID602-HC<br />

models.<br />

3.0<br />

2.5<br />

2.0<br />

1200<br />

1.5<br />

GPM CWS<br />

1.0<br />

1100<br />

1000<br />

900<br />

800<br />

700<br />

GPM CWS<br />

3.0<br />

3.0<br />

2.5<br />

2.0<br />

1.5<br />

1.0<br />

2.5<br />

2.0<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

0.4<br />

0.8<br />

0.6<br />

0.4<br />

0.3<br />

0.2<br />

0.8<br />

0.3<br />

600<br />

0.6<br />

0.4<br />

0.2<br />

500<br />

0.3<br />

400<br />

0.2<br />

300<br />

NC22<br />

"C" NOZZLES<br />

25 30 35 39<br />

200<br />

0.3" 0.4" 0.5"<br />

0.6" 0.7" 0.8" 0.9" 1.0"<br />

100<br />

0<br />

4.0<br />

NC 20 25<br />

0.3" 0.4" 0.5" 0.6"<br />

30 34<br />

"B" NOZZLES<br />

0.7" 0.8" 0.9"1.0"<br />

NC 15 20 25<br />

"A" NOZZLES<br />

0.3" 0.4" 0.6" 0.8" 1.0"<br />

6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0<br />

30.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID602-US-2 or DID602-HC-2 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID602-US-2 models)<br />

Max. Recommended GPM (DID602-HC-2 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Chilled</strong> Water Pressure Loss<br />

T INDUCED AIR - T ENTERING CHILLED WATER<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.03 No Correction Multiply by 0.91 Multiply by 0.90<br />

1.35 1.15 1.0<br />

0.9<br />

2.65 2.25 2.0<br />

1.8<br />

-5 No Correction +3<br />

+4<br />

Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15<br />

See Figure 37 (DID602-US-2) or Figure 39 (DID602-HC-2)<br />

See Table 6 (page 38)<br />

Figure 46: Cooling (2 Pipe) Performance, DID602-US-2 and DID602-HC-2<br />

45