PRIMARY AIR COOLING<br />
Net Sensible Heating Capacity, BTUH/LF<br />
WATER SIDE HEATING<br />
NET SENSIBLE HEATING<br />
Heating Performance (4-Pipe) DID602<br />
1000<br />
900<br />
800<br />
Chart is based on 6 ft. DID602-HC-4 (4<br />
pipe) heating with a 20˚F temperature<br />
differential between room and primary air<br />
and a 50˚F temperature differential<br />
between room and entering hot water.<br />
For other beam lengths, see the<br />
correction factors table below.<br />
GPMHWS<br />
GPMHWS<br />
700<br />
600<br />
500<br />
1.5<br />
1.0<br />
0.8<br />
0.6<br />
1.5<br />
1.0<br />
0.8<br />
0.6<br />
GPMHWS<br />
1.5<br />
1.0<br />
0.8<br />
400<br />
0.4<br />
0.3<br />
0.4<br />
0.6<br />
300<br />
0.2<br />
0.3<br />
0.4<br />
200<br />
0.2<br />
0.3<br />
100<br />
0.2<br />
0<br />
-100<br />
-200<br />
-300<br />
-400<br />
"A" NOZZLES<br />
NC 15 20 25<br />
0.3" 0.4" 0.6" 0.8" 1.0"<br />
-500<br />
-600<br />
"B" NOZZLES<br />
NC 20<br />
0.3" 0.4"<br />
25<br />
30 34<br />
0.5" 0.6" 0.7" 0.8" 0.9"1.0"<br />
-700<br />
"C" NOZZLES<br />
NC 22 25 30 35 39<br />
0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"<br />
4.0<br />
6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0<br />
Primary Airflow Rate, CFM/LF<br />
30.0<br />
Corrections for Other DID602-US-4 or DID602-HC-4 Lengths & T ENTERING WATER - T INDUCED AIR<br />
Performance Parameter<br />
Water Side Heating (BTUH/LF)<br />
Max. Recommended GPM (DID602-US-4 models)<br />
Max. Recommended GPM (DID602-HC-4 models)<br />
Noise Level (NC)<br />
<strong>Beam</strong> Length (Nominal Length in Feet)<br />
4 Feet 6 Feet 8 Feet<br />
10 Feet<br />
Multiply by 1.04 No Correction Multiply by 0.88 Multiply by 0.85<br />
1.5 1.5 1.5<br />
1.5<br />
1.5 1.5 1.5<br />
1.5<br />
-5 No Correction +3<br />
+4<br />
Primary Air Pressure Drop<br />
Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15<br />
Hot Water Pressure Loss See Figure 36 41<br />
TENTERING HOT WATER - TINDUCED AIR<br />
See Table 7 (page 38)<br />
Figure 50: 45: Heating (4 Pipe) Performance, DID602-US-4 and DID602-HC-4<br />