PRIMARY AIR COOLING<br />

Net Sensible Heating Capacity, BTUH/LF<br />

WATER SIDE HEATING<br />

NET SENSIBLE HEATING<br />

Heating Performance (4-Pipe) DID602<br />

1000<br />

900<br />

800<br />

Chart is based on 6 ft. DID602-HC-4 (4<br />

pipe) heating with a 20˚F temperature<br />

differential between room and primary air<br />

and a 50˚F temperature differential<br />

between room and entering hot water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

GPMHWS<br />

GPMHWS<br />

700<br />

600<br />

500<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

GPMHWS<br />

1.5<br />

1.0<br />

0.8<br />

400<br />

0.4<br />

0.3<br />

0.4<br />

0.6<br />

300<br />

0.2<br />

0.3<br />

0.4<br />

200<br />

0.2<br />

0.3<br />

100<br />

0.2<br />

0<br />

-100<br />

-200<br />

-300<br />

-400<br />

"A" NOZZLES<br />

NC 15 20 25<br />

0.3" 0.4" 0.6" 0.8" 1.0"<br />

-500<br />

-600<br />

"B" NOZZLES<br />

NC 20<br />

0.3" 0.4"<br />

25<br />

30 34<br />

0.5" 0.6" 0.7" 0.8" 0.9"1.0"<br />

-700<br />

"C" NOZZLES<br />

NC 22 25 30 35 39<br />

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"<br />

4.0<br />

6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0<br />

Primary Airflow Rate, CFM/LF<br />

30.0<br />

Corrections for Other DID602-US-4 or DID602-HC-4 Lengths & T ENTERING WATER - T INDUCED AIR<br />

Performance Parameter<br />

Water Side Heating (BTUH/LF)<br />

Max. Recommended GPM (DID602-US-4 models)<br />

Max. Recommended GPM (DID602-HC-4 models)<br />

Noise Level (NC)<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.04 No Correction Multiply by 0.88 Multiply by 0.85<br />

1.5 1.5 1.5<br />

1.5<br />

1.5 1.5 1.5<br />

1.5<br />

-5 No Correction +3<br />

+4<br />

Primary Air Pressure Drop<br />

Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15<br />

Hot Water Pressure Loss See Figure 36 41<br />

TENTERING HOT WATER - TINDUCED AIR<br />

See Table 7 (page 38)<br />

Figure 50: 45: Heating (4 Pipe) Performance, DID602-US-4 and DID602-HC-4<br />

49