Sensible Cooling Capacity, BTUH/LF<br />

PRIMARY AIR COOLING SECONDARY (WATER) COOLING<br />

TOTAL SENSIBLE COOLING<br />

Cooling Performance (4-Pipe) DID301<br />

750<br />

700<br />

650<br />

Chart is based on 6 ft. DID301-US-4 (4<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

600<br />

550<br />

500<br />

GPMCWS<br />

450<br />

400<br />

350<br />

GPMCWS<br />

1.5<br />

1.5<br />

1.0<br />

0.5<br />

0.3<br />

GPMCWS<br />

300<br />

1.0<br />

250<br />

1.5<br />

0.5<br />

0.3<br />

200<br />

1.0<br />

0.5<br />

150<br />

0.3<br />

"C" NOZZLES<br />

100<br />

NC<br />

0.2"<br />

20<br />

25 30 35 39<br />

0.3" 0.4" 0.5"<br />

0.6" 0.7" 0.8" 0.9" 1.0"<br />

50<br />

NC 15<br />

0.2"<br />

20<br />

0.3"<br />

25<br />

0.4"<br />

30<br />

0.5" 0.6"<br />

35<br />

37<br />

0.8" 1.0"<br />

"B" NOZZLES<br />

0<br />

NC 15 20 25 30 33<br />

0.3" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"A" NOZZLES<br />

2.0<br />

3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0<br />

Primary Airflow Rate, CFM/LF<br />

15.0<br />

Corrections for Other DID301-US-4 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID301-US-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.02 No Correction Multiply by 0.97 Multiply by 0.95<br />

1.5 1.5 1.5<br />

1.5<br />

-1 No Correction +1<br />

+2<br />

Multiply by 0.74 No Correction Multiply by 1.03 Multiply by 1.07<br />

<strong>Chilled</strong> Water Pressure Loss See Figure 38 43<br />

TINDUCED AIR - TENTERING CHILLED WATER<br />

See Table 6 (page 38)<br />

Figure 54: 59: Cooling (4 Pipe) Performance, DID301-US-4<br />

58