04.10.2014 Views

Chilled Beam Design Guide - TROX

Chilled Beam Design Guide - TROX

Chilled Beam Design Guide - TROX

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Specification DID600<br />

drain fittings. Unless otherwise specified, coil<br />

connections shall be bare copper for field<br />

sweating to the water supply circuit. Connections<br />

shall face upwards, be located near the left end<br />

of the beam (when viewing into the primary air<br />

connection<br />

8. (OPTIONAL) The chilled water coil shall be<br />

provided with NPT male threaded fittings where<br />

specified. These fittings must be suitable for field<br />

connection to a similar NPT female flexible hose<br />

spigot and shall be at least 1½” long to facilitate<br />

field connection (by others).<br />

9. <strong>Beam</strong>s shall be delivered clean, flushed and<br />

capped to prevent ingress of dirt.<br />

2.03 Performance<br />

1. All performance shall be in compliance with that<br />

shown on the equipment schedule. Acoustical<br />

testing shall have been performed in accordance<br />

with ISO 3741.<br />

2. Coils shall be rated in accordance with ARI<br />

Standard 410, but their cooling and heating<br />

capacities shall be established in accordance to<br />

European Standard EN15116 for the specific<br />

application on the inlet side of the submitted<br />

chilled beam. Evidence of this testing must be<br />

included in the submittal.<br />

3. Primary airflow rates shall not result in supply<br />

(primary plus induced) airflow rates in excess of<br />

80 CFM per linear foot of (two slot) beam.<br />

4. <strong>Chilled</strong> water flow rates to the beams shall be<br />

limited to that which results in a maximum ten<br />

(10) foot head loss. Water flow velocities through<br />

the beam shall not exceed 4 FPS.<br />

lowered into the grid module by adjusting the nuts<br />

connecting the threaded rods to the beam.<br />

3. Before connecting the supply water system(s) to<br />

the beams, contractor shall flush the piping<br />

system(s) to assure that all debris and other<br />

matter have been removed.<br />

4. Contractor shall perform connection of beams to<br />

the chilled water circuit by method specified (hard<br />

connection using sweated connection or<br />

connection using flexible hoses.<br />

5. Flexible connector hoses shall be furnished by<br />

others (optionally by the manufacturer). Hoses<br />

shall be twenty four (24) inches in length and<br />

suitable for operation with a bend radius as small<br />

as five (5) inches. Such hoses shall be 100%<br />

tested and certified for no leakage at 500 PSI.<br />

Connector hoses shall consist of a PFTE lined<br />

hose with a wire braided jacket. The hoses shall<br />

be suitable for operation in an environment<br />

between -40 and 200˚F, rated for a least 300 PSI<br />

and tested for leakage at a minimum pressure of<br />

360 PSI. Contractor shall assure that the chilled<br />

water supplying the beams has been properly<br />

treated in accordance to BSRIA publication AG<br />

2/93.<br />

6. No power or direct control connections shall be<br />

required for the operation of the chilled beam.<br />

3.03 Cleaning and Protection<br />

1. Protect units before, during and after installation.<br />

Damaged material due to improper site protection<br />

shall be cause for rejection.<br />

2. Clean equipment, repair damaged finishes as<br />

required to restore beams to as-new appearance.<br />

PART 3- EXECUTION<br />

3.02 Installation<br />

1. Coordinate the size, tagging and capacity of the<br />

beams to their proper location.<br />

2. (RECOMMENDED INSTALLATION<br />

PROCEDURE) <strong>Chilled</strong> beams up to six feet in<br />

length shall be independently suspended from<br />

the structure above by a four (4) threaded rods of<br />

⅜” diameter (provided by the installing<br />

contractor). For beams beyond six feet in length,<br />

six (6) threaded rods of ⅜” diameter. The upper<br />

end of the rods shall be suspended from strut<br />

channels that are a) mounted perpendicular to<br />

the beam length and b) at least four inches wider<br />

than the beam to facilitate relocation of the<br />

threaded rods along their length. The rods shall<br />

be fixed to factory mounting brackets on the<br />

beam that allow repositioning (at least four<br />

inches) along its length. The beam shall then be<br />

positioned above the acoustical ceiling grid and<br />

63

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!