Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Specification DID600<br />
drain fittings. Unless otherwise specified, coil<br />
connections shall be bare copper for field<br />
sweating to the water supply circuit. Connections<br />
shall face upwards, be located near the left end<br />
of the beam (when viewing into the primary air<br />
connection<br />
8. (OPTIONAL) The chilled water coil shall be<br />
provided with NPT male threaded fittings where<br />
specified. These fittings must be suitable for field<br />
connection to a similar NPT female flexible hose<br />
spigot and shall be at least 1½” long to facilitate<br />
field connection (by others).<br />
9. <strong>Beam</strong>s shall be delivered clean, flushed and<br />
capped to prevent ingress of dirt.<br />
2.03 Performance<br />
1. All performance shall be in compliance with that<br />
shown on the equipment schedule. Acoustical<br />
testing shall have been performed in accordance<br />
with ISO 3741.<br />
2. Coils shall be rated in accordance with ARI<br />
Standard 410, but their cooling and heating<br />
capacities shall be established in accordance to<br />
European Standard EN15116 for the specific<br />
application on the inlet side of the submitted<br />
chilled beam. Evidence of this testing must be<br />
included in the submittal.<br />
3. Primary airflow rates shall not result in supply<br />
(primary plus induced) airflow rates in excess of<br />
80 CFM per linear foot of (two slot) beam.<br />
4. <strong>Chilled</strong> water flow rates to the beams shall be<br />
limited to that which results in a maximum ten<br />
(10) foot head loss. Water flow velocities through<br />
the beam shall not exceed 4 FPS.<br />
lowered into the grid module by adjusting the nuts<br />
connecting the threaded rods to the beam.<br />
3. Before connecting the supply water system(s) to<br />
the beams, contractor shall flush the piping<br />
system(s) to assure that all debris and other<br />
matter have been removed.<br />
4. Contractor shall perform connection of beams to<br />
the chilled water circuit by method specified (hard<br />
connection using sweated connection or<br />
connection using flexible hoses.<br />
5. Flexible connector hoses shall be furnished by<br />
others (optionally by the manufacturer). Hoses<br />
shall be twenty four (24) inches in length and<br />
suitable for operation with a bend radius as small<br />
as five (5) inches. Such hoses shall be 100%<br />
tested and certified for no leakage at 500 PSI.<br />
Connector hoses shall consist of a PFTE lined<br />
hose with a wire braided jacket. The hoses shall<br />
be suitable for operation in an environment<br />
between -40 and 200˚F, rated for a least 300 PSI<br />
and tested for leakage at a minimum pressure of<br />
360 PSI. Contractor shall assure that the chilled<br />
water supplying the beams has been properly<br />
treated in accordance to BSRIA publication AG<br />
2/93.<br />
6. No power or direct control connections shall be<br />
required for the operation of the chilled beam.<br />
3.03 Cleaning and Protection<br />
1. Protect units before, during and after installation.<br />
Damaged material due to improper site protection<br />
shall be cause for rejection.<br />
2. Clean equipment, repair damaged finishes as<br />
required to restore beams to as-new appearance.<br />
PART 3- EXECUTION<br />
3.02 Installation<br />
1. Coordinate the size, tagging and capacity of the<br />
beams to their proper location.<br />
2. (RECOMMENDED INSTALLATION<br />
PROCEDURE) <strong>Chilled</strong> beams up to six feet in<br />
length shall be independently suspended from<br />
the structure above by a four (4) threaded rods of<br />
⅜” diameter (provided by the installing<br />
contractor). For beams beyond six feet in length,<br />
six (6) threaded rods of ⅜” diameter. The upper<br />
end of the rods shall be suspended from strut<br />
channels that are a) mounted perpendicular to<br />
the beam length and b) at least four inches wider<br />
than the beam to facilitate relocation of the<br />
threaded rods along their length. The rods shall<br />
be fixed to factory mounting brackets on the<br />
beam that allow repositioning (at least four<br />
inches) along its length. The beam shall then be<br />
positioned above the acoustical ceiling grid and<br />
63