Net Sensible Heating Capacity, BTUH/LF<br />

PRIMARY AIR COOLING NET SENSIBLE HEATING<br />

WATERSIDE HEATING<br />

Heating Performance (4-Pipe) DID301<br />

450 Chart is based on 6 ft. DID301-US-4 (4<br />

pipe) heating with a 20˚F temperature<br />

differential between room and primary air<br />

and an 50˚F temperature differential<br />

400 between room and entering hot water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

350<br />

GPM HWS<br />

300<br />

250<br />

200<br />

150<br />

GPM HWS<br />

0.3<br />

1.5<br />

1.0<br />

GPM HWS<br />

1.5<br />

1.0<br />

0.8<br />

0.5<br />

0.8<br />

0.5<br />

0.3<br />

1.5<br />

1.0<br />

0.8<br />

0.5<br />

100<br />

0.3<br />

50<br />

0<br />

-50<br />

-150<br />

-200<br />

NC 15 20 25 30 33<br />

0.3" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"A" NOZZLES<br />

-250<br />

NC 15<br />

0.2"<br />

20<br />

0.3"<br />

25<br />

0.4"<br />

30<br />

0.5" 0.6"<br />

35<br />

37<br />

0.8" 1.0"<br />

"B" NOZZLES<br />

"C" NOZZLES<br />

NC<br />

25 30 35 39<br />

0.3" 0.4" 0.5"<br />

0.6" 0.7" 0.8" 0.9" 1.0"<br />

2.0<br />

3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID301-US-4 Lengths & T ENTERING WATER - T INDUCED AIR<br />

Performance Parameter<br />

Water Side Heating (BTUH/LF)<br />

Max. Recommended GPM (DID301-US-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.03 No Correction Multiply by 0.96 Multiply by 0.92<br />

1.5 1.5 1.5<br />

1.5<br />

-1 No Correction +1<br />

+2<br />

Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.97<br />

Hot Water Pressure Loss See Figure 39 44<br />

T ENTERING HOT WATER - T INDUCED AIR<br />

See table 7 (page 38)<br />

Figure 61: 56: Heating (4 Pipe) Performance, DID301-US-4<br />

60