04.10.2014 Views

Chilled Beam Design Guide - TROX

Chilled Beam Design Guide - TROX

Chilled Beam Design Guide - TROX

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Passive <strong>Beam</strong> Performance<br />

<strong>Beam</strong> Width (B)<br />

(inches)<br />

24<br />

20<br />

16<br />

14<br />

Water Flow Rate<br />

(GPM)<br />

ΔP WATER , ft. H 2 O<br />

<strong>Chilled</strong> <strong>Beam</strong> Length, Ft.<br />

Sensible Cooling Capacity, (BTUH/LF)<br />

T ROOM - T CWS<br />

4 5 6 8 10 15 16 17 18 19 20 21 22<br />

0.75 1.8 1.3 1.5 1.7 2.1 153 194 236 277 318 360 401 442<br />

1.00 3.2 2.3 2.6 3.1 3.7 242 283 324 366 407 448 490 531<br />

1.25 5.0 3.6 4.1 4.8 5.8 295 336 377 418 460 501 542 584<br />

1.50 7.2 5.2 5.9 6.9 8.3 330 371 412 454 495 536 577 619<br />

1.75 0.8 0.9 1.0 1.2 1.4 354 396 437 478 520 561 602 643<br />

2.00 1.0 1.1 1.3 1.6 1.9 373 415 456 497 539 580 621 662<br />

2.25 1.3 1.4 1.6 2.0 2.4 387 429 470 511 553 594 635 677<br />

2.50 1.6 1.8 2.0 2.5 2.9 399 440 482 523 564 606 647 688<br />

2.75 1.9 2.2 2.4 3.0 3.5 409 450 491 533 574 615 656 698<br />

3.00 2.3 2.6 2.9 3.6 4.2 417 458 499 541 582 623 665 706<br />

0.75 0.9 1.1 1.2 1.5 1.7 169 204 239 273 308 343 378 413<br />

1.00 1.7 1.9 2.2 2.7 3.1 232 266 301 336 371 406 440 475<br />

1.25 2.6 3.0 3.4 4.2 4.8 267 302 337 372 407 441 476 511<br />

1.50 3.8 4.3 4.9 6.0 6.9 292 326 361 396 431 466 500 535<br />

1.75 0.6 0.7 0.8 1.0 1.1 309 343 378 413 448 483 517 552<br />

2.00 0.8 1.0 1.1 1.3 1.4 322 356 391 426 461 496 530 565<br />

2.25 1.0 1.2 1.4 1.7 1.8 332 366 401 436 471 506 540 575<br />

2.50 1.3 1.5 1.7 2.0 2.2 340 375 409 444 479 514 549 583<br />

2.75 1.6 1.8 2.0 2.5 2.7 346 381 416 451 486 520 555 590<br />

3.00 1.9 2.2 2.4 2.9 3.2 352 387 422 456 491 526 561 596<br />

0.75 0.8 0.9 1.0 1.2 1.4 168 195 221 247 274 300 326 352<br />

1.00 1.4 1.5 1.7 2.2 2.5 202 228 254 281 307 333 360 386<br />

1.25 2.1 2.4 2.7 3.4 3.9 222 249 275 301 327 354 380 406<br />

1.50 3.0 3.4 3.9 4.9 5.7 235 262 288 314 341 367 393 419<br />

1.75 0.5 0.6 0.6 0.8 1.0 245 272 298 324 350 377 403 429<br />

2.00 0.7 0.8 0.8 1.1 1.2 252 279 305 331 358 384 410 437<br />

2.25 0.8 1.0 1.1 1.3 1.6 258 284 311 337 363 389 416 442<br />

2.50 1.0 1.2 1.3 1.6 2.0 262 289 315 341 368 394 420 447<br />

2.75 1.2 1.4 1.6 2.0 2.4 266 292 319 345 371 398 424 450<br />

3.00 1.5 1.7 1.9 2.4 2.8 269 296 322 348 375 401 427 453<br />

0.75 0.6 0.7 0.8 1.1 1.3 153 176 198 221 244 266 289 311<br />

1.00 1.1 1.3 1.5 1.9 2.2 177 199 222 245 267 290 312 335<br />

1.25 1.8 2.0 2.3 3.0 3.5 191 214 237 259 282 304 327 350<br />

1.50 2.5 2.9 3.3 4.3 5.0 201 224 246 269 291 314 337 359<br />

1.75 0.4 0.5 0.6 0.7 0.8 208 231 253 276 298 321 344 366<br />

2.00 0.6 0.7 0.7 0.9 1.1 213 236 258 281 303 326 349 371<br />

2.25 0.7 0.8 0.9 1.2 1.3 217 240 262 285 308 330 353 375<br />

2.50 0.9 1.0 1.2 1.4 1.7 220 243 265 288 311 333 356 378<br />

2.75 1.1 1.2 1.4 1.7 2.0 223 245 268 291 313 336 358 381<br />

3.00 1.3 1.5 1.7 2.1 2.4 225 248 270 293 315 338 361 383<br />

NOTES REGARDING PERFORMANCE DATA:<br />

1. Sensible cooling data is based on a six (6) foot long uncapped beam with a 12" stack height (H), a ceiling free area of 50%<br />

and an air passage width (W) twice the beam width (B) per figure 17. 13.<br />

2. For other beam lengths, ceiling free areas and/or air passage widths see table 3 for correction factors.<br />

Table 2: TCB-2 Passive <strong>Beam</strong> (Two Row Coil) Cooling Performance Data<br />