PRIMARY AIR COOLING<br />
Sensible Cooling Capacity, BTUH/LF<br />
TOTAL SENSIBLE COOLING<br />
SECONDARY (WATER) COOLING<br />
Cooling Performance (4-Pipe) DID621<br />
1120<br />
1040<br />
960<br />
880<br />
Chart is based on 6 ft. DID621-HC-4 (4<br />
pipe) cooling with a 20˚F temperature<br />
differential between room and primary air<br />
and an 18˚F temperature differential<br />
between room and entering chilled water.<br />
For other beam lengths, see the<br />
correction factors table below.<br />
Performance at water flow rates > 1.5<br />
GPM is only achievable with DID621-HC<br />
models.<br />
GPMCWS<br />
800<br />
720<br />
640<br />
3.0<br />
2.5<br />
2.0<br />
GPMCWS<br />
1.5<br />
560<br />
1.0<br />
0.6<br />
480<br />
400<br />
3.0<br />
2.0<br />
1.5<br />
1.0<br />
0.6<br />
0.4<br />
0.3<br />
0.2<br />
320<br />
0.4<br />
0.3<br />
240<br />
0.2<br />
160<br />
"G" NOZZLES<br />
80<br />
NC<br />
15<br />
20<br />
25 30 35 37<br />
0<br />
NC<br />
0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"<br />
15 20 25 27<br />
0.2" 0.3" 0.4" 0.6" 0.8" 1.0"<br />
"M" NOZZLES<br />
1.0"<br />
1.0<br />
2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0<br />
Primary Airflow Rate, CFM/LF<br />
Corrections for Other DID621-US-4 or DID621-HC-4 Lengths & T INDUCED AIR - T ENTERING<br />
WATER<br />
Performance Parameter<br />
<strong>Beam</strong> Length (Nominal Length in Feet)<br />
4 feet 6 feet 8 feet<br />
10 feet<br />
Sensible Cooling (BTUH/LF)<br />
Max. Recommended GPM (DID621-US-4 models)<br />
Max. Recommended GPM (DID621-HC-4 models)<br />
Noise Level (NC)<br />
Primary Air Pressure Drop<br />
<strong>Chilled</strong> Water Pressure Loss<br />
Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.90<br />
1.5 1.35 1.2<br />
1.1<br />
3.0 2.65 2.35<br />
2.1<br />
-5 No Correction +3<br />
+6<br />
Multiply by 1.03 No Correction Multiply by .98 Multiply by .97<br />
See Figure 38 33 (DID621-US-4) or Figure 40 35 (DID621-HC-4)<br />
TINDUCED AIR - TENTERING CHILLED WATER See Table 6 (page 38)<br />
Figure 48: 53: Cooling (4 Pipe) Performance, DID621-US-4 and DID621-HC-4<br />