PRIMARY AIR COOLING<br />

Sensible Cooling Capacity, BTUH/LF<br />

TOTAL SENSIBLE COOLING<br />

SECONDARY (WATER) COOLING<br />

Cooling Performance (4-Pipe) DID621<br />

1120<br />

1040<br />

960<br />

880<br />

Chart is based on 6 ft. DID621-HC-4 (4<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

Performance at water flow rates > 1.5<br />

GPM is only achievable with DID621-HC<br />

models.<br />

GPMCWS<br />

800<br />

720<br />

640<br />

3.0<br />

2.5<br />

2.0<br />

GPMCWS<br />

1.5<br />

560<br />

1.0<br />

0.6<br />

480<br />

400<br />

3.0<br />

2.0<br />

1.5<br />

1.0<br />

0.6<br />

0.4<br />

0.3<br />

0.2<br />

320<br />

0.4<br />

0.3<br />

240<br />

0.2<br />

160<br />

"G" NOZZLES<br />

80<br />

NC<br />

15<br />

20<br />

25 30 35 37<br />

0<br />

NC<br />

0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"<br />

15 20 25 27<br />

0.2" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"M" NOZZLES<br />

1.0"<br />

1.0<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID621-US-4 or DID621-HC-4 Lengths & T INDUCED AIR - T ENTERING<br />

WATER<br />

Performance Parameter<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 feet 6 feet 8 feet<br />

10 feet<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID621-US-4 models)<br />

Max. Recommended GPM (DID621-HC-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Chilled</strong> Water Pressure Loss<br />

Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.90<br />

1.5 1.35 1.2<br />

1.1<br />

3.0 2.65 2.35<br />

2.1<br />

-5 No Correction +3<br />

+6<br />

Multiply by 1.03 No Correction Multiply by .98 Multiply by .97<br />

See Figure 38 33 (DID621-US-4) or Figure 40 35 (DID621-HC-4)<br />

TINDUCED AIR - TENTERING CHILLED WATER See Table 6 (page 38)<br />

Figure 48: 53: Cooling (4 Pipe) Performance, DID621-US-4 and DID621-HC-4<br />

52