AIR CONDITIONING
AIR CONDITIONING
AIR CONDITIONING
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
2.2.3 Assignment - EDIO2<br />
The assignment depends on the unit version (DX1, DX2, CW). Explanation see page 7.<br />
Pin Designation DX1 DX2 CW<br />
1 Din 20 free ext. alarm 4 free<br />
2 Din 21 free free free<br />
3 Din 22 Pump failure 3 Pump failure 3 free<br />
4 Din 23 Pump failure 4 Pump failure 4 free<br />
5 Din 24 free free free<br />
6 Din 25 free free free<br />
7 Din 26 free free free<br />
8 Din 27 free free free<br />
9 Dout 14 (NO)<br />
10 Dout 14 (COM)<br />
11 Dout 14 (NC)<br />
12 Dout 15 (NO)<br />
13 Dout 15 (COM)<br />
14 Dout 15 (NC)<br />
15 Dout 16 (NO)<br />
16 Dout 16 (COM)<br />
17 Dout 16 (NC)<br />
18 Dout 17 (NO)<br />
19 Dout 17 (COM)<br />
20 Dout 17 (NC)<br />
21 Dout 18 (NO)<br />
22 Dout 18 (COM)<br />
23 Dout 18 (NC)<br />
24 Dout 19 (NO)<br />
25 Dout 19 (COM)<br />
26 Dout 19 (NC)<br />
27 PWM3 electronical<br />
28 GND<br />
expansion valve 2<br />
29 PWM4<br />
30 GND<br />
Pump 3 Pump 3 free<br />
Pump 4 Pump 4 free<br />
free Humidifier on/off /ENS free<br />
Drycooler 3 Drycooler 3 free<br />
Drycooler 4 Drycooler 4 free<br />
free free free<br />
electronical<br />
expansion valve 2<br />
free<br />
free free free<br />
X10 SUB-D 15 Bus 3 I 2 C (plug) Bus 3 I 2 C (plug) Bus 3 I 2 C (plug)<br />
E/1006/57/11