C7000 Advanced<br />

Info<br />

Runtimes<br />

The runtimes of the listed components<br />

are shown in hours in the following windows<br />

at the bottom of the page.<br />

C7000 PT2<br />

The functional runtimes in detail:<br />

The unit runtime comprises all times when<br />

at least one component is operating.<br />

The stoptime is counted when the unit is<br />

in local stop or timer stop or remote stop<br />

or bms-stop.<br />

The cooling runtime is counted each time<br />

when cooling is requested.<br />

The heating runtime is counted each time<br />

when heating is requested.<br />

The humidification runtime is the total<br />

runtime of all humidifiers.<br />

The dehumidification runtime is counted<br />

each time the solenoid valve for cutting a<br />

part of the evaporator is activated/closed<br />

or the fan speed is reduced for dehumidification<br />

reasons (DX-size 1 and all<br />

CW-units).<br />

The functional runtimes include the<br />

same components as for the C7000<br />

Advanced.<br />

Info/Runtimes □ 27<br />

→U.start 180 h<br />

U.stop 120 h<br />

U.cooling 125 h<br />

U.heating 123 h<br />

U.humi 145 h<br />

U.dehumi 260 h<br />

Event-Log<br />

All alarm messages and events of one A/C<br />

unit are listed in this window. The messages<br />

contain the following information:<br />

alarm text, day and time. When the unit<br />

was started and stopped is also displayed.<br />

Up to 200 events can be stored.<br />

Info/Events □ 27<br />

→13.11 Start<br />

12.11 Unit on<br />

11.11 Unit off<br />

System<br />

In this menu the software version, the<br />

hardware version and the unit type are<br />

displayed.<br />

The field "more" shows that there is another<br />

window.<br />

Here the number of connected EAIO-,<br />

EDIO- and EBUS-boards is indicated, the<br />

same as optional extensions of the software.<br />

E/1006/57/37