5.2 Start - C7000 Advanced<br />

After having switched on the power supply of the C7000 Advanced the window<br />

at the right side will appear. On this window the maximum number of 32 bus<br />

participants (bus-ID 0 - 31) are displayed by symbols which are located in 8<br />

columns and 4 lines. An I/O controller is displayed by a square frame with an<br />

indication of the local temperature and humidity in integer values. A grey frame<br />

signifies that the unit is in a stop state, a black frame indicates that the unit is<br />

in operation. An IOC symbol without measured values indicates that the IOC is<br />

not reachable; e.g. because it is switched off (no voltage) or due to a bus fault.<br />

The other symbols contain an abbreviation for the controller type: PT - C7000<br />

Plus Terminal, PT2 - C7000 Plus Terminal2, AT - C7000 Advanced Terminal,<br />

ME - C7000AT at which these windows are actually displayed.<br />

The bus-ID can be deducted from the location in the scheme. Line 1 contains<br />

the bus participants 0 - 7 from left to right, line 2: 8-15, line 3: 16-23, line 4:<br />

24-31.<br />

A space signifies that a unit with a corresponding bus-ID does not exist.<br />

A symbol/unit which is selected, is displayed inversely. In the window on top of<br />

the page the C7000AT is selected. It appears inversely with white letters on a<br />

black background. In the window below, the C7000IOC is selected.<br />

The context status line contains the bus-ID and the global address of the<br />

selected bus participant.<br />

The global status line contains the Stulz logo, the bus-ID and global address<br />

of the AT from which you operate and the clock.<br />

context status line<br />

global status line<br />

With the selector key you can choose the unit which you want to control. After<br />

having marked the last bus participant position 31 you get to the following<br />

display, with the selector key, where all units are marked. In this state you can<br />

switch on/off the whole system by the local on/off key.<br />

If some units are in operation, all units are switched off if you press the on/off<br />

key. Then, with the second key activation all units are switched on.<br />

If you press the OK-button when all positions are marked the checkbus function<br />

is carried out (after the request and entry of the service master password).<br />

Getting further with the selector key brings you via the Stulz logo to the bus-ID<br />

of the AT which you have the possibility to adjust (after the request and entry<br />

of the service master password) and to the global address which cannot be<br />

adjusted here, for safety reasons.<br />

Finally you can adjust the time by selecting the clock.<br />

The following items can be adjusted in sequence:<br />

bus-ID<br />

global address<br />

- Year<br />

- Month<br />

- Day<br />

- Hour<br />

- Minute<br />

- Second<br />